本文以成都市某高效制冷机房为研究对象,基于 2023年全年实测运行数据,通过系统的数据处理方法,建立了系统能效评价及运行参数分析方法.结果表明:经筛选后的运行数据整体呈现稳定运行规律.该制冷机房全年平均能效比为5.69,但在自控测试阶段受设备运行模式切换影响,系统能效表现存在明显波动;供回水温差及运行模式对系统能效具有显著影响,理论最优冷却温差约为 5℃,而当前控制水平约为 4℃,系统仍具节能优化潜力.分项能耗分析显示冷水机组为系统主要能耗设备,冷却塔及水泵运行策略对系统综合能效亦有重要影响.

A high-efficiency refrigeration plant room in Chengdu is examined in this study based on annual operational data from 2023.By applying systematic data processing methods,an approach for evaluating system efficiency and analyzing operational parameters is established.The results show that the filtered operational data exhibited stable patterns.The plant achieved an annual average energy efficiency ratio of 5.69,although significant efficiency fluctuations occurred during the automatic control testing phase due to equipment mode switching.Further analysis indicates that both the supply-return temperature difference and operating modes have a substantial impact on system efficiency.The theoretically optimal chilled water temperature difference is approximately 5℃,whereas the current operational level is about 4℃,indicating potential for energy-saving optimization.Component-level energy consumption analysis reveals that chillers are the primary energy-consuming equipment,while the operational strategies of cooling towers and pumps also significantly influence overall system efficiency.

邱安龙

厦门海辰储能科技股份有限公司,福建 厦门 361000

能源科技

高效制冷机房能效评价运行参数

High-efficiency chilled water plantEnergy efficiency evaluationOperational parameter

《制冷技术》 2026 (3)

58-63,6

10.3969/j.issn.2095-4468.2026.03.203