温度分布及绝缘表面凝露对SF6绝缘柱上真空断路器内部电场的影响OA

Influence of Temperature Distribution and Surface Condensation on the Internal Electric Field of SF6-insulated Pole-mounted Vacuum Circuit Breakers

中文摘要英文摘要

柱上开关作为配网中的关键设备,其稳定运行直接关系到电网的供电安全.近年来柱上开关故障频发,故障案例解体分析表明设备密封老化失效导致内部受潮是直接诱因.鉴于受潮与设备内部温度分布以及电场畸变之间密切相关,并最终引发绝缘劣化失效.为此,文中以ZW20-12/630 A型真空断路器为例,仿真研究了温度及绝缘表面凝露对开关内部电场的畸变.首先根据ZW20型柱上开关CAD图纸建立了二维仿真模型,采用有限元软件Ansys maxwell仿真计算了正常设备内部的介质及导体损耗,进而通过fluent软件计算了开关内部温度场分布,并将温度场数据导入到电场计算模块,根据温度分布修正材料介电常数,得到计及温度作用下的电场分布情况;在设备易受潮部位添加凝露模型,研究了3种不同受潮缺陷情况对电场分布的影响.结果表明:设备内部温度分布和表面凝露对设备内部电场造成了不同程度的畸变,进线套管部位等部分区域电场畸变甚至超出气体绝缘介质的耐电强度,极易引发局部放电并进而诱发绝缘故障.文中的研究成果对于解释柱上开关受潮引发绝缘故障的机理,并发展相应的检测手段奠定了理论基础.

Pole-mounted switch is a critical equipment in distribution network,and its stable operation is essential to the safety of power grid.In recent years,the pole-mounted witch has experienced frequent failures.Post-failure disassembly analysis shows that moisture ingress caused by aging failure of equipment seal is the direct contributign factor.Given that moisture ingress is closely correlated with the internal temperature distribution and electric field distortion within the equipment,it ultimately leads to insulation degradation and failure.To this end,in this paper type ZW20-12/630 A vacuum circuti breaker is taken as an example to study and simulate the distortion of the inter-nal electric field caued by temperature and surface condensation on the insulation.First,a two-dimensional simula-tion model is established based on the CAD drawings of the pole-mounted switch.The finite element software Ansys maxwell is used to simulate and calculate the dielectric and conductor losses inside the normal equipment.Then,the internal temperature filed distribution of the pole-mounted switch is calculated through fluent software,the oba-tined temperature field data is imported into the electric filed calculation module,where the dielectric constant of the material is corrected in accordance with the temperature distribution,thereby obtaining the electric field distri-bution taking into account the temperature.The condensation model is added to the moisture-prone parts of the pole-mounted switch to study the influence of three moisture conditions on the electric field distribution.The results show that both internal temperature distribution and surface condensation cause varying degree of electric fieldd dis-tortion inside the equipment.The electric field distrotion in certain area such as incoming bushing area even ex-ceeds the dielectric strength of the gas insulated medium,which can readily trigger partial discharge and subse-quently lead to insulation failure.The research results in this paper lay a theoretical foundation for explaining the mechanism of insulation failure caused by moisture on the pole-mounted switch and developing the corresponding detection methods.

桂媛;马光耀;王智晖;朱成昊;徐若旋;李昕玥;刘士驹;唐志国

国网北京市电力公司电力科学研究院,北京 100192国网北京市电力公司,北京 100031国网北京市电力公司电力科学研究院,北京 100192国网北京市电力公司大兴供电公司,北京 102600华北电力大学,北京 102206华北电力大学,北京 102206华北电力大学,北京 102206华北电力大学,北京 102206

温度场受潮凝露电场分布柱上开关

temperature fieldmoisturecondensationelectric field distributionpole-mounted switch