多台超超临界机组负荷分配及其综合能效分析OA

Comprehensive energy efficiency analysis of multiple ultra-supercritical units and load distribution strategy

中文摘要英文摘要

[目的]燃煤电厂厂级电负荷分配方式影响其经济性,为揭示某电厂多台超超临界机组能效特性的差异及电负荷分配对全厂经济性的影响,提出最优电负荷分配策略,以实现全厂运行节能增效.[方法]本文以某电厂一期2×1 000 MW超超临界一次再热机组和二期2×1 000 MW超超临界二次再热机组为对象,基于Ebsilon软件平台建立一、二期机组的热力系统模型,模拟纯凝工况下以5%为步长、30%THA~100%THA共15个负荷点时,一、二期机组的煤耗及热耗率变化规律.[结果]研究表明,在电负荷为300 MW至1 000 MW之间,一期机组煤耗率区间为277.1~310.9 g/(kW·h),最大差值为33.8 g/(kW·h);而二期机组煤耗率区间为266.8~297.6 g/(kW·h),最大差值为30.8 g/(kW·h).低负荷时,单位电负荷变化对煤耗率的影响更显著.一期机组在低负荷下煤耗率降幅更大;高负荷时,二期机组经济性更优,2 200 MW总负荷下,一期多带负荷方案热耗率较二期低30.26 kJ/(kW·h).[结论]机组负荷分配需动态优化,总负荷较低时优先由一期机组承担,随着总负荷升高需逐步增加二期机组负荷比例,高负荷时段由二期机组主导,可显著降低全厂煤耗.

[Objective]The plant-level electric load distribution mode of coal-fired power plant affects its economy.In order to reveal the difference of energy efficiency characteristics of multiple ultra-supercritical units in a power plant and the influence of electric load distribution on the economy of the whole plant,the optimal electric load distribution strategy is proposed to realize the energy saving and efficiency increase of the whole plant operation.[Methods]In this paper,the 2×1 000 MW ultra-supercritical single-reheat unit in the first phase and the 2×1 000 MW ultra-supercritical double-reheat unit in the second phase of a power plant are taken as the object.Based on the Ebsilon software platform,the thermal system models of the first and second phase units are established.The variation of coal consumption and heat consumption rate of the first and second phase units is simulated under the condition of pure condensation with 5%step size and 30%THA~100%THA,a total of 15 load points.[Results]The results show that when the electric load is between 300 MW and 1 000 MW,the coal consumption rate of the first stage unit is 277.1~310.9 g/(kW·h),and the maximum difference is 33.8 g/(kW·h).The coal consumption rate of the second phase unit is 266.8~297.6 g/(kW·h),and the maximum difference is 30.8 g/(kW·h).At low load,the influence of unit electric load change on coal consumption rate is more significant.The coal consumption rate of the first-stage unit decreases more under low load;under high load,the economy of the second-stage unit is better.Under the total load of 2 200 MW,the heat consumption rate of the first-stage multi-load scheme is 30.26 kJ/(kW·h)lower than that of the second-stage.[Conclusion]The load distribution of the unit needs to be dynamically optimized.When the total load is low,it is preferentially borne by the first-stage unit.As the total load increases,the load ratio of the second-stage unit needs to be gradually increased.The high-load period is dominated by the second-stage unit,which can significantly reduce the coal consumption of the whole plant.

张海峰;刘庆同;陈国庆;殷戈;高行龙;周小明

国能常州第二发电有限公司,江苏 常州 213001河海大学机电工程学院,江苏 常州 213022低碳智能燃煤发电与超净排放全国重点实验室(国家能源集团科学技术研究院有限公司),江苏 南京 210023低碳智能燃煤发电与超净排放全国重点实验室(国家能源集团科学技术研究院有限公司),江苏 南京 210023国能常州第二发电有限公司,江苏 常州 213001河海大学电气与动力工程学院,江苏 南京 211100

能源科技

燃煤机组负荷分配能效分析热力系统建模超超临界机组

coal-fired power uniteconomic analysisthermodynamic system modelingultra-supercritical units

《电力科技与环保》 2026 (4)

582-590,9

低碳智能燃煤发电与超净排放全国重点实验室开放课题(D2023FK092)江苏省特种设备安全监督检验研究院项目(KJ(Y)202409)

10.19944/j.eptep.1674-8069.2026.04.007

评论