首页|期刊导航|电气技术|智能汇聚压板在线监测方案研究及应用

智能汇聚压板在线监测方案研究及应用OA

Research and application of online monitoring solution for intelligent convergence of terminal block

中文摘要英文摘要

当前,变电站二次回路出口压板连接状态缺乏可靠且有效的监测方法,难以支撑继电保护运维人员及时排查相关回路缺陷.现有监测方案多通过传感器感知压板连片状态来判断投退情况,只能间接确认压板状态,原理存在局限,识别可靠性不足.为此,本文研究自扩展式保护压板智能感知技术,实现压板状态实时精准检测,支持与保信系统双向通信.厂站端硬压板采集选用成熟可靠的保护及智能终端装置,数据传输采用通用成熟的 IEC 61850 标准与面向通用对象的变电站事件(GOOSE)通信技术,既保障数据传输可靠性,又符合电力网络安全防护要求.该方案实施简便、经济实用,采用硬压板自主采集模式,依托现有数据通信网络搭建传输体系,无需新建专用系统,可实现智能汇聚接入与功能灵活扩展.经试点变电站验证,方案可行且有效,能够防范硬压板误投退引发的继电保护不正确动作,提升电网第一道防线运行风险辨识与主动防御能力,增强电网运行安全性.

At present,substations lack a reliable and effective monitoring method for the connection status of outlet pressing plates in secondary circuits,making it difficult to guide relay protection operators to detect such secondary circuit defects in a timely manner.Existing schemes sense the pressing plate contacts through sensors and other means to judge whether the pressing plate is switched on,which can only indirectly confirm the pressing plate status in principle and lead to unreliable identification results.This paper studies a self-extensible intelligent sensing technology for relay protection pressing plates,which can realize real-time detection of pressing plate status and support bidirectional communication with the relay protection information system.For the acquisition of hard pressing plates at the substation side,mature and reliable protection devices and intelligent terminal devices are adopted,while the public and mature IEC 61850 standard and generic object oriented substation event(GOOSE)communication technology are used for data uploading,ensuring the reliability of data transmission and complying with network security protection requirements.The proposed scheme is simple,feasible,economical and practical.It adopts self-acquisition of hard pressing plates and constructs a data transmission scheme based on the existing data communication network without building an independent system,realizing intelligent convergence access and functional expansion.The feasibility and effectiveness of the scheme are verified through pilot substation applications.It can prevent incorrect operation events of relay protection caused by mis-switching of hard pressing plates,improve the operation risk identification and active defense capability of the first line of defense of the power grid,and enhance the security of power grid operation.

周陈斌;石一峰;孟屹华;邓立晨;周斌

国网江苏省电力有限公司苏州供电分公司,江苏 苏州 215000国网江苏省电力有限公司苏州供电分公司,江苏 苏州 215000国网江苏省电力有限公司苏州供电分公司,江苏 苏州 215000国网江苏省电力有限公司苏州供电分公司,江苏 苏州 215000国网江苏省电力有限公司苏州供电分公司,江苏 苏州 215000

双联压板智能监测自扩展保信接入

double-terminal blockintelligent monitoringself-extendingprotection information system integration

《电气技术》 2026 (9)

50-54,5