广州市某数据中心空调系统节能改造案例分析OA
Case Study of Energy Efficiency Retrofit for the HVAC System of a Data Center in Guangzhou
针对现有数据中心空调系统改造过程中存在需要保障业务不中断和场地紧张的情况,本文根据广州市某数据中心改造工程提出一种可实现上述改造要求,同时不影响非改造区域正常运行的应用案例以供参考.该案例通过建设保障冷源系统实现改造过程中IT设备运行的空调需求;待保障冷源系统稳定运行后,建设一套新的高温冷水系统.经测算,改造区域数据机房满足年PUE≤1.3,较原有降低12.7%,当全年室外空气湿球温度≤13 ℃的小时数能达1,580h,较不自然冷却模式,利用板式换热器的自然冷却使得年PUE降低约1%.
To address the challenges of ensuring business continuity and managing limited space during the retrofitting of existing data center air conditioning systems,this paper presents a case study of a retrofitting project in a Guangzhou data center.This case study meets these requirements without affecting the normal operation of non-retrofit areas.The implementation involves first constructing a backup cooling system to meet the air conditioning demands of IT equipment during the renovation.Once this system is stably operational,a new high-temperature chilled water system is constructed.Calculations indicate that the retrofitted data center zone achieves an annual PUE of 1.3 or less,representing a 12.7%reduction compared to the pre-retrofit system.Furthermore,given 1,580 annual hours with an outdoor air wet-bulb temperature at or below 13° C,the implementation of natural cooling via a plate heat exchanger lowers the annual PUE by approximately 1%relative to the scenario without natural cooling.
林敏聪
广东省建科建筑设计院有限公司,广州,510013
建筑与水利
数据中心保障冷源系统高温冷水PUE自然冷却
Data CenterCooling System AssuranceHigh-temperature Chilled WaterPower Usage EffectivenessFree Cooling
《制冷》 2026 (4)
10-16,7