医用质子重离子加速器冷却水系统用电量控制状态评估研究OA

Evaluation study on electricity consumption control state of medical proton and heavy ion accelerator cooling water system

中文摘要英文摘要

目的:研究医用质子重离子加速器冷却水系统热负荷、环境温度和用电量的关系,以评估用电量控制状态.方法:首先,基于医用质子重离子加速器冷却水系统结构和热负荷分析,提出负荷强度系数计算方法.然后,以月度为计量周期,以2021-2024年某医院医用质子重离子加速器冷却水系统48个月的相关数据作为样本进行数据拟合,根据环境温度均值、负荷强度系数和用电量数据拟合结果得出月度用电量的预测方程.以拟合优度R2评价拟合结果,通过月度差值比例系数DCi评估用电量的控制状态.结果:多项式拟合方程的R2为0.930 84,通过月度用电量的预测方程得到的估计用电量和实际用电量的变化趋势一致;DCi 分布形态接近正态分布,用电量控制状态为中等的月份最多,并沿两侧降低,进一步验证了拟合结果的可信度.结论:该研究明确了影响质子重离子加速器冷却水系统用电量的核心因素,可有效评估医用质子重离子加速器冷却水系统用电量控制状态.

Objective To investigate the relationship between the thermal load,ambient temperature and electricity consum-ption of the medical proton and heavy ion accelerator cooling water system,so as to evaluate its electricity consumption con-trol state.Methods Firstly,a load intensity factor calculation method was proposed based on the structure and thermal load analyses of the cooling water system of the medical proton and heavy ion accelerator.Then,the 48-month data related to the medical proton and heavy ion accelerator cooling water system of some hospital from 2021 to 2024 was used as a sample for data fitting in a monthly measurement period,and the prediction equation for monthly electricity consumption was derived with the fitting results of the mean ambient temperature,load intensity factor and electricity consumption data.The fitting results were evaluated by the goodness-of-fit R2,and the control state of electricity consumption was assessed with the monthly difference ratio coefficient DCi.Results The R2 of the polynomial fitting equation was 0.930 84,and the estimated electricity consumption obtained by the prediction equation had a consistent trend with the actual electricity consumption;DCi had a nearly normal distribution.The number of months with a medium electricity consumption control state was the highest and the month numbers decreased along both sides,further validating the credibility of the fitting results.Conclusion The core factors for the electricity consumption of the medical proton and heavy ion accelerator cooling water system are clarified,which contribute to evaluating effectively the electricity consumption control state of the medical proton and heavy ion accelerator cooling water system.[Chinese Medical Equipment Journal,2026,47(9):78-85]

李万宏;朱春杰

上海市质子重离子医院,上海市放射肿瘤学重点实验室,上海质子重离子放射治疗工程技术研究中心,上海 201321上海市质子重离子医院,上海市放射肿瘤学重点实验室,上海质子重离子放射治疗工程技术研究中心,上海 201321

医药卫生

医用质子重离子加速器冷却水系统用电量控制多项式拟合医疗设备管理

medical proton and heavy ion acceleratorcooling water systemelectricity consumption controlpolynomial fitting equationmedical equipment management

《医疗卫生装备》 2026 (9)

78-85,8

上海市科学技术委员会生物医药领域定向项目(22DX1900200)上海市医院协会医院建筑后勤管理专业委员会课题研究专项

10.19745/j.1003-8868.2026146