首页|期刊导航|煤气与热力|新风参数对主动式冷梁空调系统性能影响实验

新风参数对主动式冷梁空调系统性能影响实验OA

Experiment on Influence of Fresh Air Parameters on Performance of Active Chilled Beam Air Conditioning Systems

中文摘要英文摘要

设计一种主动式冷梁结合空气喷射器的冷梁空调系统实验系统.采用实验方法,对新风参数对冷梁空调系统制冷效果、性能的影响进行研究.标准实验工况:压缩空气供气温度25℃、供气压力0.7 MPa、供气流量9.08 m3/h,冷梁冷水进水温度17℃、质量流量0.11 t/h.新风温度对冷梁空调系统降温效果的影响远大于新风流量,降低新风温度可显著提升室内降温效果,而单纯增大新风流量作用有限.在满足房间必要新风量前提下,采用夏季典型室外温度(30~35℃)的新风,可使冷梁空调系统获得较理想的性能.新风温度一定时,不宜采用过大新风流量.冷梁供冷房间内温度竖向分布存在明显空间差异,距冷梁越近竖向温度分布越复杂,距冷梁越远则越接近传统热分层.

An experimental system for a chilled beam air conditioning system combining an active chilled beam with an air ejector was designed.An experimen-tal method was adopted to investigate the influence of fresh air parameters on the cooling effect and perfor-mance of the chilled beam air conditioning system.The standard experimental conditions are as follows:com-pressed air supply temperature of 25℃,supply pres-sure of 0.7 MPa,supply flow rate of 9.08 m3/h,chilled beam chilled water inlet temperature of 17℃,and mass flow rate of 0.11 t/h.The influence of fresh air temperature on the cooling performance of the chilled beam air conditioning system is much greater than that of fresh air flow rate.Reducing the fresh air tempera-ture can significantly improve the indoor cooling effect,whereas simply increasing the fresh air flow rate has a limited effect.On the premise of meeting the necessary fresh air demand of the room,using fresh air at typical summer outdoor temperatures(30-35℃)can achieve satisfactory performance of the chilled beam air condi-tioning system.When the fresh air temperature was constant,an excessively high fresh air flow rate is not recommended.Obvious spatial differences exist in the vertical temperature distribution in the room cooled by the chilled beam.The vertical temperature distribution is more complex closer to the chilled beam,and becomes closer to the traditional thermal stratification farther away from it.

李鑫;郑文科;魏瑞宁;曹慧哲;黄子健;姜益强

哈尔滨工业大学 建筑与设计学院,黑龙江 哈尔滨 150006||寒地城乡人居环境科学与技术工业和信息化部重点实验室,黑龙江 哈尔滨 150090哈尔滨工业大学 建筑与设计学院,黑龙江 哈尔滨 150006||寒地城乡人居环境科学与技术工业和信息化部重点实验室,黑龙江 哈尔滨 150090哈尔滨工业大学 建筑与设计学院,黑龙江 哈尔滨 150006||寒地城乡人居环境科学与技术工业和信息化部重点实验室,黑龙江 哈尔滨 150090哈尔滨工业大学 建筑与设计学院,黑龙江 哈尔滨 150006||寒地城乡人居环境科学与技术工业和信息化部重点实验室,黑龙江 哈尔滨 150090哈尔滨工业大学 建筑与设计学院,黑龙江 哈尔滨 150006||寒地城乡人居环境科学与技术工业和信息化部重点实验室,黑龙江 哈尔滨 150090哈尔滨工业大学 建筑与设计学院,黑龙江 哈尔滨 150006||寒地城乡人居环境科学与技术工业和信息化部重点实验室,黑龙江 哈尔滨 150090

建筑与水利

主动式冷梁空气喷射器新风参数制冷效果

active chilled beamair ejectorfresh air parameterscooling effect

《煤气与热力》 2026 (9)

22-28,7