不同气候区变电站建筑围护结构传热系数限值OA
Limit Values of Heat Transfer Coefficients for Building Envelopes of Substations in Different Climate Zones
对不同气候区(各气候区选取1座典型城市)变电站建筑围护结构传热系数限值进行研究.屋面、外窗传热系数保持不变,哈尔滨、北京、昆明变电站的节能率均随外墙传热系数减小而增大,上海、广州变电站的节能率均随外墙传热系数增大而增大.外墙、外窗传热系数保持不变,哈尔滨、北京、昆明变电站的节能率均随屋面传热系数减小而增大,上海、广州变电站的节能率均随屋面传热系数增大而增大.与调节屋面传热系数相比,同一气候区内,基本上调节外墙传热系数的节能潜力更高.而屋面长期受太阳辐射直射,得热量大,同样是变电站围护结构节能改造的关键部位.严寒地区B、寒冷地区B、夏热冬冷地区、夏热冬暖地区、温和地区变电站外墙传热系数限值分别为0.300、0.320、1.150、1.480、1.200 W/(m2·K),屋面传热系数限值分别为0.200、0.450、0.800、0.900、0.700 W/(m2·K).
The limit values of heat transfer coefficients for substation building envelopes across different cli-mate zones,with one typical city selected for each zone,were investigated.When the heat transfer coeffi-cients of roofs and external windows remain unchanged,the energy-saving rates of substations in Harbin,Beijing and Kunming increase as the external wall heat transfer coefficient decreases.By contrast,the energy-saving rates of substations in Shanghai and Guangzhou increase as the external wall heat transfer coefficient increases.When the heat transfer coeffi-cients of external walls and external windows are kept constant,the energy-saving rates of substations in Har-bin,Beijing and Kunming grow with the reduction of the roof heat transfer coefficient,whereas those in Shanghai and Guangzhou increase as the roof heat transfer coefficient rises.Within the same climate zone,adjusting the heat transfer coefficient of external walls generally provides greater energy-saving poten-tial than adjusting that of roofs.Meanwhile,roofs are exposed to long-term direct solar radiation with large heat gain,making them also a key component for energy-saving renovation of substation building enve-lopes.The heat transfer coefficient limits of substation exterior walls in severe cold area B,cold area B,hot summer and cold winter area,hot summer and warm winter area,and mild area are 0.300,0.320,1.150,1.480,and 1.200 W/(m2·K).The roof heat transfer coef-ficient limits are 0.200,0.450,0.800,0.900,and 20.700 W/(m2·K).
冯云哲;王昭俊;张圣金;牟文博
哈尔滨工业大学 建筑与设计学院,黑龙江 哈尔滨 150006||寒地城乡人居环境科学与技术工业和信息化部重点实验室,黑龙江 哈尔滨 150090哈尔滨工业大学 建筑与设计学院,黑龙江 哈尔滨 150006||寒地城乡人居环境科学与技术工业和信息化部重点实验室,黑龙江 哈尔滨 150090中国能源建设集团黑龙江省电力设计院有限公司,黑龙江 哈尔滨 150078哈尔滨工业大学 建筑与设计学院,黑龙江 哈尔滨 150006||寒地城乡人居环境科学与技术工业和信息化部重点实验室,黑龙江 哈尔滨 150090
建筑与水利
变电站建筑围护结构传热系数建筑节能
substation buildingbuilding enclosureheat transfer coefficientbuilding energy-saving
《煤气与热力》 2026 (9)
17-21,36,6
评论