以北京某居民楼为例,分析供暖需求,研究了空气源热泵额定制热量对室内温度、空气源热泵供暖负荷率与能效的影响.空气源热泵额定制热量分别取建筑设计热负荷的1.0、1.2、1.4倍,记为配置1、2、3.配置1时,共910 h不能满足供暖室内设计温度18℃的供暖要求,占供暖期的31.34%.配置2时,共564 h不能满足供暖室内设计温度18℃的供暖要求,占供暖期的19.42%.配置3时,共284 h不能满足供暖室内设计温度18℃的供暖要求,占供暖期的9.78%.配置1、2、3空气源热泵供暖期平均负荷率分别为 71.2%、63.6%、56.5%,耗电量分别为 1 346.97、1 568.44、1 853.07 kW·h,运行费用分别为700.42、815.59、963.60 元,折合单位面积费用分别为10.81、12.59、14.87 元/m2,低于目前集中供暖24~30 元/m2的收费标准.配置3时,空气源热泵的制热性能系数在供暖初期和末期较高.空气源热泵制热性能系数大于 3.0的时间为 2 170 h,占供暖期的74.72%,制热性能系数大于3.5的时间共计1 553 h,占供暖期的53.48%,制热性能系数大于4.0的时间共计1 015 h,占比为34.95%.空气源热泵分散供暖与区域锅炉房集中供暖相比具有节能优势.对于北京的居民小区,推荐按照建筑设计热负荷的1.4倍配置空气源热泵额定制热量,其运行费用最低.

Taking a residential building in Beijing as an example,the heating demand was analyzed and the impact of the rated heating capacity of air-source heat pumps(ASHP)on the indoor temperature,heating load rate and energy efficiency of ASHP was studied.Three rated heating capacity schemes are set as 1.0,1.2 and 1.4 times the building design heating load,denoted as Scheme 1,Scheme 2 and Scheme 3.Under Schemes 1,2 and 3,the durations with indoor temperature below the designed heating temperature of 18 ° C are 910 h(31.34%),564 h(19.42%)and 284 h(9.78%)of the whole heating season,respectively.The average heat-ing load rates of ASHPs during the heating season for Scheme 1,2 and 3 are 71.2%,63.6%and 56.5%corre-spondingly.Their total power consumptions are 1,346.97 kW·h,1,568.44 kW·h and 1,853.07 kW·h,with corresponding operating costs of 700.42 CNY,815.59 CNY and 963.60 CNY.The equivalent unit-area costs are 10.81 CNY/m2,12.59 CNY/m2 and 14.87 CNY/m2,all lower than the current central heat-ing charge standard of 24-30 CNY/m2.For Scheme 3,the coefficient of performance(COP)of ASHPs is rela-tively high in the early and late stages of the heating season.During the heating season,the system operates 2,170 hours(74.72%)at a COP exceeding 3.0,1,553 hours(53.48%)above COP 3.5,and 1,015 hours(34.95%)above COP 4.0.Decentralized heating based on air-source heat pumps delivers energy-saving advan-tages compared with central heating supplied by dis-trict boiler rooms.For residential communities in Bei-jing,it is recommended to configure the rated heating capacity of ASHPs at 1.4 times the building design heating load,which yields the lowest operating cost.

杨采婷;胡文举;张浩扬

北京建筑大学 供热、供燃气、通风及空调工程北京市重点实验室,北京 100044北京建筑大学 供热、供燃气、通风及空调工程北京市重点实验室,北京 100044||北京建筑大学 北京节能减排与城乡可持续发展协同创新中心,北京 100044北京建筑大学 供热、供燃气、通风及空调工程北京市重点实验室,北京 100044

建筑与水利

空气源热泵额定制热量室内温度供暖负荷率能效

air-source heat pumprated heating capac-ityindoor temperatureheating load rateenergy effi-ciency

《煤气与热力》 2026 (9)

11-16,6

评论