以PE-RT Ⅱ型塑料管道为研究对象,通过对带保温和无保温的PE-RT Ⅱ型塑料管进行散热损失测试,分析其保温性能.通过测试,计算PE-RT Ⅱ型塑料管当量粗糙度,与钢管进行对比,分析其减阻效果.在相同保温层与外护层条件下,PE-RT Ⅱ型塑料管保温结构综合热阻比钢管提高了4.7%,聚氨酯保温层仍是直埋供热管道保温性能的主要保证.PE-RT Ⅱ型塑料管相较于钢管,随着流量增加减阻效果越发明显.

Taking PE-RT Ⅱ plastic pipelines as the research object,heat loss tests are performed on insu-lated and noninsulated PE-RT Ⅱ plastic pipes to ana-lyze their thermal insulation performance.The equiva-lent roughness of PE-RT Ⅱ pipes is calculated from testing data,and the dragreduction performance is ana-lyzed by comparison with steel pipes.With the same insulation and external protective layer,the overall thermal resistance of the insulation system for PE-RTⅡ pipes is 4.7%higher than that of steel pipes.The polyurethane foam layer is the main guarantee of ther-mal insulation performance for directly buried heating pipelines.Compared with steel pipes,PE-RT Ⅱ plas-tic pipes exhibit increasingly prominent drag-reduction performance as the flow rate rises.

杨硕;冯文亮;甄浩然;王松川

北京北燃实业集团有限公司,北京 100023北京市公用事业科学研究所有限公司,北京 100011||北京市建设工程质量第四检测所有限公司,北京 100011北京市公用事业科学研究所有限公司,北京 100011||北京市建设工程质量第四检测所有限公司,北京 100011北京北燃供热有限公司,北京 100023

建筑与水利

PE-RTⅡ型塑料管单位管道长度散热量沿程阻力

PE-RT Ⅱ plastic pipeheat loss per unit pipe lengthfrictional resistance

《煤气与热力》 2026 (9)