换流变套管SF6气体分解物异常与防范策略研究OA
Research on Abnormal SF6 Gas Decomposition Products in Converter Transformer Sleeve and Prevention Strategies
套管中的 SF6 气体仅具有绝缘功能,并且设备在运行过程中一般不会发生局部放电,导致其中 SF6 气体产生分解物的原因复杂.通过分解物成分和含量可以判断套管内部的运行工况.文中分析了某直流±500 kV 换流变阀侧套管 SF6 气体分解物异常事故,通过分解物成分检测、解体检查、耐压试验和通流试验等技术手段,推理、论证了 SO2 和其他污染物产生的原因和故障机理,并提出针对性防范措施,为类似问题和隐患的防范、处理提供借鉴和依据.
The SF6 gas in the casing only has insulation function,and the equipment generally does not undergo partial discharge during operation.It is necessary to conduct in-depth research on why SF6 gas produces decomposition products under this working condition.The operating conditions inside the casing can be determined by the composition and content of the decomposition products.This article analyzes the first abnormal SF6 gas decomposition accident on the side sleeve of a DC±500 kV converter valve in Chi-na.Through tests such as decomposition component detection,disassembly inspection,voltage withstand test,and current flow test,the causes and failure mechanisms of SO2 and other pollutants are inferred and demonstrated,and targeted preventive measures are proposed.The research content and achievements of the article fill the gap in this technical field,providing valuable reference and basis for the prevention and treatment of similar problems and hidden dangers.
张宏伟
国网甘肃省电力公司 金昌供电公司,甘肃省金昌市新华路78号 737100
信息技术与安全科学
直流输电套管SF6 气体绝缘分解物低能量放电
direct current transmissioncasingSF6 gas insulationdecomposition productslow ener-gy discharge
《河北水利电力学院学报》 2026 (3)
47-55,9
评论