目前,现场气体绝缘开关(gas insulated switchgear,GIS)设备的局部放电缺陷检测主要是依赖于PZT传感系统,但其性能已难以满足电力设备高水平运维需求.近年来,诸多研究团队开展了干涉型光纤声发射传感技术的研究.但目前大部分的研究仅是注重于提升光纤传感器的灵敏度,忽略对于传感器复用性能的研究,无法实现分布式感知.为此,提出一种基于双Mach-Zehnder光纤干涉的声发射检测方法,该方法既可实现对高频信号的高灵敏度检测,并能利用信号到达2个Mach-Zehnder干涉仪的时间差进行信源辨识,以此实现GIS局部放电的分布式声学检测.围绕此方法,对双Mach-Zehnder光纤干涉传感系统的关键参数进行设计,并搭建实验平台对系统的响应性能和定位性能进行测试.此外,基于真实1 10kVGIS开展了局部放电检测实验,评估光纤传感系统对于金属微粒缺陷的检测水平.实验结果表明,基于双Mach-Zehnder干涉光纤声发射传感系统检测信噪比比PZT传感系统高约5dB.此外,该系统可实现20个传感单元的串联复用,信号作用点定位误差为4.62 m.将光纤传感阵列中的20个传感单元安装在GIS各个腔室表面,即可根据信号作用位置确定缺陷所在腔体,以此实现GIS局部放电缺陷的分布式感知及定位.

Currently,partial discharge defect detection in on-site gas insulated switchgear(GIS)equipment mainly relies on PZT sensing systems,but their performance is insufficient to meet the high-level operation and maintenance require-ments of power equipment.In recent years,many research teams have conducted research on interferometric fiber optic acoustic emission sensing technology.However,most current research focuses only on improving the sensitivity of fiber optic sensors,neglecting the research on sensor multiplexing performance,thus failing to achieve distributed sensing.To address this issue,we propose an acoustic emission detection method based on dual Mach-Zehnder fiber optic interferom-etry.This method can achieve high-sensitivity detection of high-frequency signals and utilize the time difference of signal arrival at the two Mach-Zehnder interferometers for source identification,thereby realizing distributed acoustic detection of partial discharge in GIS.Based on this method,we design the key parameters of the dual Mach-Zehnder fiber optic in-terferometric sensing system and build an experimental platform to test the system's response and positioning performance.Furthermore,a partial discharge detection experiment was conducted on a real 110 kV GIS to evaluate the detection level of the fiber optic sensing system for metal particle defects.Experimental results show that the sig-nal-to-noise ratio of the dual Mach-Zehnder interferometric fiber optic acoustic emission sensing system is approximately 5 dB higher than that of the PZT sensing system.Furthermore,this system can achieve cascaded multiplexing of 20 sens-ing units with a signal application point positioning error of 4.62 m.By installing the 20 sensing units in the fiber optic sensing array on the surface of each chamber in the GIS,the cavity containing defects can be determined based on the signal application location,thereby realizing distributed sensing and localization of partial discharge defects in GIS.

李朝辉;徐智新;赵鑫成;谢鹏;周宏扬

国网福建省电力有限公司超高压分公司,福州 350000国网福建省电力有限公司超高压分公司,福州 350000国网福建省电力有限公司超高压分公司,福州 350000国网福建省电力有限公司超高压分公司,福州 350000厦门理工学院电气工程与自动化学院,厦门 361024

气体绝缘开关局部放电光纤传感声发射分布式

gas insulated switchgearpartial dischargeoptical fiber sensingacoustic emissiondistributed

《高电压技术》 2026 (8)

3515-3523,9

国网福建省电力有限公司科技项目(52130A250004).Project supported by State Grid Fujian Electric Power Company Science and Technology Project(52130A250004).