当前数据中心普遍采用"短链路、多分支"配电架构,若为各支路单独配置直流断路器,虽可实现可靠隔离,但总投资随支路数大幅上升.为此,提出一种不含全控型器件的限流式多端口直流断路器(CLMP-DCCB).首先分阶段对 CLMP-DCCB 的工作过程进行理论解析;进而分析电压、电流应力与拓扑关键参数间的相互关系,提出相应的参数设计方法;最后通过 MATLAB/Simulink 平台对所提出的 CLMP-DCCB 与相关典型方案进行对比仿真.结果表明,该方案在降低系统综合成本与提升开断性能方面具备显著优势,为 CLMP-DCCB 在数据中心配电系统中的应用提供了有效的技术支撑.
Current data centers widely adopt a"short-link,multi-branch"power distribution architecture.While individually configuring DC circuit breakers for each branch can achieve reliable isolation,the total investment increases significantly with the number of branches.To address this,a current-limiting multi-port DC circuit breaker(CLMP-DCCB)without fully-controlled devices is proposed.The working process of the CLMP-DCCB is first theoretically analyzed in stages.Subsequently,the relationships among voltage stress,current stress,and key topological parameters are examined,and a corresponding parameter design method is proposed.Finally,a comparative simulation is conducted on MATLAB/Simulink between the proposed CLMP-DCCB and relevant typical schemes.The results demonstrate that this solution offers significant advantages in reducing overall system costs and enhancing breaking performance,providing effective technical support for the application of CLMP-DCCB in power distribution systems of data center.
邱伟杰;缪希仁
福州大学 电气工程与自动化学院,福建 福州 350108福州大学 电气工程与自动化学院,福建 福州 350108
信息技术与安全科学
数据中心多端口直流断路器晶闸管耦合电感
data centermulti-port DC circuit breakerthyristorcoupled inductor