基于线路零序相频特性的谐振接地系统主动区段定位OA
Feeder Zero Sequence Frequency Response Based Section Positioning Technology for Resonant Grounding Systems
该文基于现代电网日益显著的电力电子化特征,提出一种中性点谐振接地系统单相接地故障主动区段定位技术.通过连续电磁暂态时域分析建立信号产生和提取方法;分析故障和非故障路径下游线路零序频率响应,研究故障和非故障区段首、末端零序相频特性变化规律及其电流信号表征方法,进而建立基于单端或双端信号相频特性的故障区段判定依据.该技术无需外加信号产生装置,配电终端也无需配置电压互感器,可与现有基于各种故障特征的接地故障区段定位方法形成互补,仿真和模拟实验都验证了该方法的有效性.
The single-phase-to-ground faults account for approximately 80%of all faults in the distribution network,necessitating accurate and reliable fault location to ensure power system security and stability.Due to the influence of different grounding modes,traditional passive location methods based on transient or steady-state features often lack location sensitivity under high-resistance grounding or small fault initial angles,owing to weak characteristic signals.Existing active signal injection methods typically require additional signal-injection equipment and are limited by monotonous signal features and a lack of anti-interference capability.Considering the development of the double-high power system,a reliable identification of the section affected by a ground fault can be achieved by a characteristic controllable current signal generated by the power electronics employed to switch the damping resistor in the arc-suppression coil.This method requires no additional signal-injection equipment,maintains identification accuracy under interference,and eliminates the need for potential transformers at terminal units. When the single-phase-to-ground fault enters a steady state,the damping resistor is periodically switched for short durations by controlling the delay triggering angle δ of the anti-parallel thyristor applied to the damping resistor in the arc suppression coil,generating a transient current disturbance in the zero-sequence circuit.The characteristic signal is then accurately extracted from the zero-sequence current—which contains power frequency components and background noise—by employing a full-cycle subtraction combined with a multi-signal polarity correction mean algorithm.Furthermore,establishing the zero-sequence harmonic impedance at the beginning and end of the section,and constructing the phase information indicator θav based on the characteristic frequency band.Based on the indicator above,the double-end and single-end section location criteria are established to cope with the various operating conditions. Results from Matlab simulations based on the topology of an actual 10 kV distribution network line,as well as simulated experiments employing the method of reducing the entire network voltage,indicate that the disturbance signal is concentrated in the low-frequency band below 100 Hz,and the signal strength increases significantly with the increase of δ.Besides,the phase difference indicator θcr between the sending and receiving ends of the faulted section remains consistently and significantly positive,therefore the faulted section can be identified accurately in both the simulation tests and simulated experiments.Sensitivity analysis confirms that the θcr of the faulted section remains more than 10° larger than that of the healthy sections under the combined effects of high fault resistance,long cable lines,and measurement errors caused by asynchronism.Furthermore,comparative analysis verifies that the proposed method can accurately locate the fault under conditions of a fault inception angle of 5° and a fault resistance of 2 kΩ,while the existing methods based on transient reactive power or current increment exhibit abnormal location results. According to the analysis above,the following conclusions can be drawn:(1)The proposed section location method generates distinct and controllable signal characteristics,which facilitates the detection and extraction of fault signals under the interference of factors such as fault resistance.(2)The variation in the zero-sequence phase-frequency characteristics of the section can be obtained to determine the faulted section by utilizing the generated current signal,eliminating the need for voltage measurement data.(3)The proposed method identifies the faulted section based on changes in the zero-sequence phase-frequency characteristics,a criterion that is independent of the grounding fault type and is minimally affected by fault location and resistance.(4)The signal strength affects the accuracy and synchronization of the signals detected at each terminal,which in turn impacts the precise acquisition of the difference in zero-sequence phase-frequency characteristics between the sending and receiving ends of the section.The signal strength can be increased by controlling δ.
单田宝;李亚辉;高文博;朱珂
山东大学电网智能化调度与控制教育部重点实验室 济南 250061山东大学电网智能化调度与控制教育部重点实验室 济南 250061山东大学电网智能化调度与控制教育部重点实验室 济南 250061山东大学电网智能化调度与控制教育部重点实验室 济南 250061
信息技术与安全科学
区段定位相频响应消弧线圈晶闸管配电网
Section positioningphase frequency responsearc suppression coilthyristordistribution network
《电工技术学报》 2026 (17)
5878-5889,12