一起接地开关联锁功能失效故障分析OA
Fault Analysis of Ground Switch Interlock Function Failure
某 500 kV 变电站现场验收期间发现接地开关联锁异常,表现为隔离开关合闸状态下,就地合闸按钮仍可使接地开关电机得电运行.虽然机械联锁阻断了接地开关合闸操作,但电气回路缺陷构成严重安全风险.经回路排查,确认故障原因是电动操作回路中自保持回路火线与就地合闸回路火线错接,该接线错误导致就地控制时合闸回路可导通但自保持功能失效.更正接线后,远方和就地两种操作模式下接地开关防误功能均恢复正常.本案例分析为同类采用接地开关的变电站提供了技术参考.
During the on-site acceptance of a certain 500 kV substation,it finds that the interlock of the ground switch is abnormal.It manifests that when the disconnector is closed,the local closing button could still make the ground switch motor energized and operate.Although mechanical interlocking blocks the closing operation of the ground switch,electrical circuit defects pose a serious safety risk.After circuit investigation,it confirms that the cause of the fault is the wrong connection between the live wire of the self-holding circuit and the live wire of the local closing circuit in the electric operation circuit.This wiring error leads to the closing circuit being able to conduct during local control,but the self-holding function fails.After correcting the wiring,the anti-misoperation function of the ground switch returns to normal in both remote and local operation modes.This case analysis provides an technical reference for similar substations that adopt ground switches.
王常乐;张明;朱宁俊
国网江苏省电力有限公司南京供电分公司,江苏 南京 210000国网江苏省电力有限公司南京供电分公司,江苏 南京 210000国网江苏省电力有限公司南京供电分公司,江苏 南京 210000
信息技术与安全科学
接地开关电机回路电气联锁变电站防误操作
ground switchmotor circuitelectrical interlocksubstationanti-misoperation
《东北电力技术》 2026 (8)
17-21,27,6