首页|期刊导航|Energy and Built Environment|Experimental investigation of building mock-ups and air source heat pumps in cold climates

Experimental investigation of building mock-ups and air source heat pumps in cold climatesOA

中文摘要

Air source heat pumps(ASHPs)are critical in reducing carbon emissions,particularly in extreme cold climates like Canada.However,less than 10% of residential buildings in Canada utilize heat pumps,underscoring the need for more energy-efficient solutions to achieve net-zero and passive house standards.This study simultaneously evaluates the performance of building mock-ups and a commercial ASHP at extremely cold temperatures of 0℃,-10℃,and-25℃,simulated in a climatic chamber using co-heating and traditional disaggregate methods.Two envelope types are evaluated:one constructed to meet the requirements of the Canadian Building Code(CBC)and another with retrofitted walls aimed at enhancing the insulation.The envelope’s thermal performance shows a deviation of no more than 7%between the co-heating and disaggregate methods,while theoretical calculations show deviations of up to 23%.The ASHP data reveal that enhanced insulation not only limits the envelope’s heat loss but also significantly improves the ASHP performance by consuming less energy while maintaining a steady thermal output.At-10℃,the retrofitted envelope increases the ASHP performance by 28%and by 100%at-25℃,relative to the performance of the CBC.These findings underscore the importance of improved building envelopes in enhancing ASHP performance and delivering sustainable heating solutions for cold climates.

Ahmed Jafri;Eric Villenuve;Martin Agelin-Chaab;Horia Hangan

Faculty of Engineering and Applied Science,Ontario Tech University,Oshaw1,ON L1G 0C5,CanadaAutomotive Centre of Excellence,Ontario Tech University,Oshaw1,ON L1G 0C5,CanadaFaculty of Engineering and Applied Science,Ontario Tech University,Oshaw1,ON L1G 0C5,CanadaFaculty of Engineering and Applied Science,Ontario Tech University,Oshaw1,ON L1G 0C5,Canada

建筑与水利

Co-heatingHeat pumpHeat transfer coefficientHeat loss parameterCOP

《Energy and Built Environment》 2026 (3)

P.654-671,18

10.1016/j.enbenv.2025.02.003