首页|期刊导航|四川水力发电|硬梁包水电站导叶锁锭信号故障分析与双重优化实践

硬梁包水电站导叶锁锭信号故障分析与双重优化实践OA

Fault analysis and dual optimization practice of guide vane locking signal at Yingliangbao Hydropower Station

中文摘要英文摘要

导叶接力器锁锭位置信号是硬梁包水轮发电机组开停机流程的关键判断条件,直接影响机组启停的可靠性与时效性.硬梁包水电站机组采用欧姆龙 D4A-4509N 接触器开关作为锁锭位置传感器,在实际运行中出现了因机械触点疲劳形变导致的信号误报问题,造成开停机流程受阻.文章结合现场故障现象与传感器工作原理,分析了信号异常的根本原因,提出了传感器选型优化与监控自动化逻辑改进的双重方案,并总结了优化实施后的运行效果.

The guide vane servomotor locking position signal is a critical judgment condition in the startup and shutdown processes of the generating units at Yingliangbao Hydropower Station,which directly affects the reli-ability and timeliness of unit operation.Yingliangbao Hydropower Station units adopt Omron D4A-4509N con-tactor switches as locking position sensors.In actual operation,false signal reporting issues have occurred due to mechanical contact fatigue deformation,causing disruptions in startup and shutdown processes.This paper combines on-site fault phenomena with sensor working principles,analyzes the root causes of signal abnormali-ties,proposes a dual optimization plan involving sensor selection improvement and monitoring automation logic enhancement,and summarizes the operational effects after optimization implementation.

刘韧;周大鹏;蒋伟;祝炳宏;李烁

四川华能泸定水电有限公司,四川 泸定 626100四川华能泸定水电有限公司,四川 泸定 626100四川华能泸定水电有限公司,四川 泸定 626100四川华能泸定水电有限公司,四川 泸定 626100四川华能泸定水电有限公司,四川 泸定 626100

能源科技

导叶接力器锁锭开停机流程欧姆龙微动传感器

guide vane servomotor lockingstartup and shutdown processesOmron micro-switch sensor

《四川水力发电》 2026 (4)

54-57,67,5

10.20196/j.cnki.scslfd.20260412

评论