水相变能与空气源双热源耦合热泵供暖实验OA
Experimental Study on Coupled Heat Pump Heating System with Water Phase-Change Energy and Air-Source Dual Heat Sources
设计水相变能与空气源双热源耦合热泵系统,对取热单元的3种取热方式进行分析.以办公建筑为供暖对象,采用实验方法,对3种取热方式下室内温度、热泵机组制热性能系数进行测试分析.方式A:套管式相变换热器单独运行,方式B:翅片管风冷换热器单独运行,方式C:套管式相变换热器与翅片管风冷换热器耦合运行.室外温度-6~-1 ℃时,方式B无法满足最低室内温度要求,方式A与方式C均可满足最低室内温度要求.与方式A相比,虽然方式C的平均室内温度稍低,但热泵机组平均制热性能系数更高.对方式B,室外温度对热泵机组性能影响较大.在室外温度较低时,应尽量采用方式A、方式C.在评价热泵机组运行效果时,不能单凭制热性能系数,还应考虑室内温度.
A coupled heat pump heating system with water phase-change energy and air-source dual heat sources was designed,and three heat extraction meth-ods of the heat extraction unit were analyzed.Taking an office building as the heating target,experimental methods were employed to test and analyze indoor tem-perature and heat pump unit heating performance coef-ficient under the three heat extraction methods.Method A:The shell-type phase-change heat exchanger operates independently.Method B:The finned-tube air-cooled heat exchanger operates inde-pendently.Method C:The shell-type phase-change heat exchanger and finned-tube air-cooled heat exchanger operate in a coupled manner.When the out-door temperature ranges from-6 to-1 ℃,Method B fails to meet the minimum indoor temperature require-ments,while Methods A and C satisfies the minimum indoor temperature requirements.Compared with Method A,Method C presents a slightly lower average indoor temperature but a higher average heating COP of the heat pump unit.For Method B,the outdoor tem-perature exerts a significant impact on the performance of the heat pump unit,and the unit still fails to meet the minimum indoor temperature demand at an outdoor temperature of-6 to-1 ℃.When the outdoor tempera-ture is relatively low,Methods A and C are recom-mended for adoption.When assessing the operation performance of the heat pump unit,it is not feasible to rely solely on the heating COP,and the indoor tempera-ture should also be taken into full account.
王森;张昌建;罗景辉;平天祎;姜钊乐
河北工程大学能源与环境工程学院,河北邯郸 056038||河北省暖通空调工程技术创新中心,河北邯郸 056038河北工程大学能源与环境工程学院,河北邯郸 056038河北工程大学能源与环境工程学院,河北邯郸 056038||河北省暖通空调工程技术创新中心,河北邯郸 056038河北工程大学能源与环境工程学院,河北邯郸 056038||河北省暖通空调工程技术创新中心,河北邯郸 056038河北工程大学能源与环境工程学院,河北邯郸 056038||河北省暖通空调工程技术创新中心,河北邯郸 056038
建筑与水利
双热源耦合热泵水相变能取热方式制热性能系数
dual-source coupled heat pumpwater phase-change energyheat extraction methodheating performance coefficient
《煤气与热力》 2026 (8)
11-16,6
中央引导地方科技发展资助项目(236Z4310G)
评论