两种重力式热管的换热特性OA

Heat transfer characteristics of two types of gravity heat pipes

中文摘要英文摘要

热管是一种高效的传热元件,因结构简单、传热性能优异等特性被广泛应用在各种场合.设计2种不同的重力热管,研究充注介质R134a在充注率15%—35%下,不同流量对2种热管的传热性能的影响.结果表明:随着充注率的增加,热管传热系数呈现先增大后减小的趋势,在充注率为30%时,铝制热管与不锈钢热管传热系数均达到峰值,分别为17.25、12.06 W/(m2·K).随着冷水流量从0.3 m3/h增加到2 m3/h,热管功率呈现上升趋势.定义铝制热管与不锈钢热管传热系数比值,在充注率为35%时铝制热管相对不锈钢热管传热系数达到最大.在相同工况下,铝制热管比不锈钢热管功率提高35.58%,铝制热管热阻整体低于不锈钢热管,两者在充注率为30%时达到最小值.用韦伯数对热管进行评价,结果表明不锈钢热管相较于铝制热管更稳定.

Heat pipes are highly efficient heat transfer components and are widely used in various applications due to their simple structure and excellent heat transfer performance.Two types of heat pipes made of different materials were designed,and the influence of different flow rates on the heat transfer performance of the two heat pipes was studied when the filling rate of the refrigerant R134a was 15%-35%.The results show that as the filling rate increases,the heat transfer coefficient of the heat pipe first increases and then decreases.When the filling rate is 30%,the heat transfer coefficients of the aluminum heat pipe and the stainless steel heat pipe reach their peaks,which are 17.25 and 12.06 W/(m2·K),respectively.As the cold water flow rate increases from 0.3 m3/h to 2 m3/h,the power of the heat pipe shows an upward trend.The ratio of the heat transfer coefficients of the aluminum heat pipe to the stainless steel heat pipe was defined.When the filling rate is 35%,the heat transfer coefficient of the aluminum heat pipe relative to the stainless steel heat pipe reaches its maximum.Under the same working conditions,the power of the aluminum heat pipe is 35.58%higher than that of the stainless steel heat pipe,and the thermal resistance of the aluminum heat pipe is generally lower than that of the stainless steel heat pipe,both reach their minimum values when the filling rate is 30%.The heat pipes were evaluated using the Weber number,indicating that the stainless steel heat pipe is more stable than the aluminum heat pipe.

朱梦锴;张昌建;罗景辉;王硕;平天祎;王森

河北工程大学 能源与环境工程学院,河北邯郸 056038||河北省暖通空调工程技术创新中心,河北邯郸 056038河北工程大学 能源与环境工程学院,河北邯郸 056038||河北省暖通空调工程技术创新中心,河北邯郸 056038河北工程大学 能源与环境工程学院,河北邯郸 056038河北工程大学 能源与环境工程学院,河北邯郸 056038||河北省暖通空调工程技术创新中心,河北邯郸 056038河北工程大学 能源与环境工程学院,河北邯郸 056038||河北省暖通空调工程技术创新中心,河北邯郸 056038河北工程大学 能源与环境工程学院,河北邯郸 056038||河北省暖通空调工程技术创新中心,河北邯郸 056038

能源科技

重力热管相变气液两相流传热充注率

gravity heat pipesphase changegas-liquid two phase flowheat transferfilling rate

《化学工程》 2026 (8)

42-47,6

中央引导地方科技发展资金项目(236Z4310G)

10.3969/j.issn.1005-9954.2026.08.008

评论