通过对西北地区已投运的60余座750 kV变电站站外工频电场强度及工频磁感应强度的系统性监测与数据采集,本研究获取了具有代表性的实测数据集.经多维度统计分析与综合评估表明:750 kV变电站厂界工频电场强度分布于0.6~3 840.0 V/m之间,工频磁感应强度介于0.014~24.330 μT范围,二者均符合国家规定的公众暴露限值要求(工频电场强度4 000 V/m、工频磁感应强度100 μT).值得注意的是,工频电场强度标准限值占比相对较高,且强度最大值普遍出现在750 kV出线侧厂界区域.因此,在750 kV变电站选址过程中,需统筹考虑进出线侧方位布局与周边居民区的空间关系.本研究成果具有双重应用价值:一方面,可为《中华人民共和国生态环境法典》中输变电工程排污许可管理制度的实施提供一定的基础数据支撑;另一方面,可为750 kV变电站的规划选址、工程设计与优化、运行维护及电磁环境监管提供科学可靠的实测依据与理论支持,进而提升超高电压等级变电站的环境兼容性及公众接受度.
By conducting systematic monitoring and data collection on power frequency electric field strength and power frequency magnetic field strength outside over 60 operational 750 kV substations in Northwest China,this study established a representative measured dataset.Multivariate statistical analysis and comprehensive assessment show that the power frequency electric field strength at the substation boundaries ranges from 0.6 to 3 840.0 V/m,while the power frequency magnetic field strength varies from 0.014 to 24.330 μT.Both parameters comply with the public exposure control limits specified in the Mandatory national standard,which stipulates a limit of 4 000 V/m for power frequency electric field and 100 μT for power frequency magnetic field.Notably,the maximum measured electric field values approach the standard limit with a small safety margin,and the peak field strength generally appears at the boundary near the 750 kV outlet side.Therefore,the layout of incoming and outgoing lines and their spatial correlation with surrounding residential areas shall be comprehensively considered during site selection for 750 kV substations.The research results carry dual practical value.On the one hand,they can provide fundamental data support for implementing the pollutant discharge permit system for power transmission and transformation projects under the"Environmental Protection Law of the People's Republic of China".On the other hand,they offer scientific,reliable measured data and theoretical support for the planning,site selection,design optimization,operation&maintenance,and electromagnetic environment supervision of 750 kV EHV substations,thus improving the environmental compatibility and public acceptance of extra-high voltage substations.
贠彦祺;宋伟宏;茜强;毛洁;蔡奥
甘肃省核与辐射安全中心 兰州 730020甘肃省核与辐射安全中心 兰州 730020甘肃省核与辐射安全中心 兰州 730020甘肃省核与辐射安全中心 兰州 730020酒泉市生态环境综合事务中心 酒泉 735000
资源环境
750 kV变电站电磁环境工频电场强度工频磁感应强度
750 kV substationElectromagnetic environmentPower frequency electric field intensityPower frequency magnetic field intensity
《辐射研究与辐射工艺学报》 2026 (4)
139-145,7
评论