首页|期刊导航|清华大学学报(自然科学版)|变压器电弧故障爆炸荷载模拟方法和抗爆平衡设计

变压器电弧故障爆炸荷载模拟方法和抗爆平衡设计OA

Load simulation of arc fault induced explosion of oil-immersed transformer and anti-explosion balance design

中文摘要英文摘要

油浸式变压器一旦发生电弧故障,可能引发变压器爆炸,甚至继发火灾和燃爆等事故,严重影响电力系统的安全运行.为研究油浸式变压器电弧故障爆炸荷载和箱体响应特性,该文首先介绍了基于LS-DYNA平台模拟电弧故障的3种数值模拟方法,即TNT等效法、瞬时注气法和匀速注气法;其次,以某500 kV变压器为例,对比分析了 3种方法的适用性;再次,基于匀速注气法揭示了电弧故障爆炸荷载的时空特征;最后,结合变压器箱体响应特征,提出了变压器结构的抗爆平衡设计思想.结果表明:相较于TNT等效法和瞬时注气法,匀速注气法能更好地模拟电弧故障爆炸荷载的升压和持压特性,有效复现电弧故障产气的持时过程,变压器结构响应特性更接近实际情况;电弧故障爆炸荷载在空间和时间上均呈快速衰减趋势,局部作用显著,且在压力波传播路径复杂区域,冲量会被显著放大;变压器结构抗爆设计过程可分为初步设计、平衡设计和泄爆设计3个阶段,并分别采用均布荷载、简化电弧故障荷载和流固耦合荷载模型进行设计.该文研究结果可为油浸式变压器的抗爆设计和优化提供参考.

[Objective]The arc fault of oil-immersed transformers may result in explosions and corresponding fire accidents,which severely affect the safe operation of the power system.However,arc fault tests cannot be conducted on a large scale due to their high cost,implementation difficulty,and low repeatability.As a result,numerical simulations have become an important research method.Various types of simulation methods are available,and the validity and applicability of their numerical results and underlying physical processes need to be examined.[Methods]Taking a 500 kV transformer as an example,this study used LS-DYNA to compare the effectiveness of the TNT equivalent method,instantaneous gas injection method,and uniform gas injection method in terms of spatial and temporal characteristics of arc fault explosion load of oil-immersed transformer.Thereafter,the response characteristics and failure modes of the structure,along with the influence of complex internal structures on the propagation of pressure,were explored.[Results]The research results indicated the following:(1)The simulations revealed that the uniform gas injection method could reproduce the process of gas production during arc faults and efficiently reflect the effect of arc fault duration,with the generated peak pressure and pressure gradient closely matching the experimental data.The instantaneous gas injection method and TNT equivalent method yielded higher loads and might overestimate the structural responses.However,they could be employed for examining weak points of transformer structures during explosions because of their simple implementation.The uniform gas injection method was suited for precise response analysis and ultimate pressure limit analysis of transformer structures,which required high accuracy.(2)The arc fault load presented a rapid attenuation characteristic in space and time,which enhanced its local effect on the structure.However,due to the spatial limitations of the transformer structure and the space occupation of internal components,the reflection and superposition of pressure waves prevented the pressure from monotonically attenuating in time and space after reaching its peak.The multi-peak characteristics of the internal explosion pressure waves intensified the impulse within the complex structure.(3)Under the considered conditions,plastic deformation of the structure occurred in the turret structure immediately adjacent to the failure location.Bending deformation arose in the tank wall near the failure area,and substantial stress concentration was observed at the corner of the tank.Under high-energy conditions,the possible failure locations were found in the local area near the arc failure and the stress concentration points at the corners.The overall bending deformation could absorb energy and expand the fluid volume within the structure,which allowed the structure to withstand explosion loads.(4)An anti-explosion balance design concept for transformers was proposed,in which different load models were used for preliminary design,balance design,and pressure-relief design.The three stages corresponded to the static pressure bearing condition,the typical fault condition,and the rare occurrence condition.[Conclusions]The uniform gas injection method effectively describes the gas generation process of the arc fault,and the load characteristics agree well with the test results.The arc fault load decays rapidly in time and space.Moreover,the complex pressure propagation path inside the transformer will considerably affect the local load.Based on the load and response characteristics,the stepwise balanced design concept adopting different levels of working conditions can improve the anti-explosion performance and realize economic benefits by simply strengthening the structure.

陈素文;郭泽琛;李贤敏;曲光磊;谢强

同济大学土木工程防灾减灾全国重点实验室,上海 200092||同济大学土木工程学院,上海 200092同济大学土木工程学院,上海 200092同济大学土木工程学院,上海 200092特变电工沈阳变压器集团有限公司,沈阳 110000同济大学土木工程防灾减灾全国重点实验室,上海 200092||同济大学土木工程学院,上海 200092

信息技术与安全科学

油浸式变压器电弧故障数值模拟荷载特性抗爆平衡设计

oil-immersed transformerarc faultnumerical simulationload characteristicsanti-explosion balance design

《清华大学学报(自然科学版)》 2026 (7)

1329-1338,10

10.16511/j.cnki.qhdxxb.2026.26.010

评论