高压直流直挂储能最低开关频率追踪控制研究OA
Research on Minimum Switching Frequency Tracking Control for High-Voltage DC Direct-Connected Energy Storage
高压直流直挂储能采用模块化多电平串联结构,布置于直流系统线路正负极之间,可支撑直流电压,配合柔性直流换流器实现功率平抑、双端构网及故障穿越等功能,但直流直挂储能存在总体开关频率高、电力电子器件损耗大、输出电流含纹波等问题.针对上述问题,首先,分析高压直流直挂储能稳态输出特性,推导出纹波峰峰值与子模块开关频率的计算方法;然后,设计直流直挂储能的最低开关频率追踪控制,使储能在支撑直流电压的同时,追踪使开关频率最低的直流电压工作点,并提出影响储能开关频率的各参数设计方法;最后,通过仿真与硬件在环实验,验证了所提开关频率计算的准确性,并证明所提控制策略可大幅降低子模块开关频率与损耗,实现总体开关频率从 10 kHz 降低至 500 Hz,同时直流电压仅降低 0.006 4(pu).
The high-voltage direct current direct-connected energy storage(HVDC-DCES)adopts a modular multilevel series structure.It is arranged between the positive and negative poles of the DC system line.It can support DC voltage and,in cooperation with the flexible DC converter,enable functions such as power smoothing,double-terminal grid forming,and fault ride-through.However,HVDC-DCES faces problems such as a high overall switching frequency and output current ripple.To address these issues,this paper derived a formula for the switching frequency of HVDC-DCES and designed a minimum switching-frequency tracking(MSFT)control strategy that utilizes the functional relationship between the switching frequency and the DC voltage.The HVDC-DCES with MSFT control can track the optimal DC voltage operating point and reduce the switching frequency. Firstly,the topology and control strategy of HVDC-DCES were briefly introduced.The discrete,stepped-voltage output characteristic of HVDC-DCES results in high-frequency switching actions,and the rounding function in the controller introduces randomness.Subsequently,the rounding function was replaced with a bias-relay function with a hysteresis loop,and the formulas for the output current ripple amplitude and switching frequency of HVDC-DCES were derived.When the switching frequency is lower than the control frequency,the output is a parabolic function of the difference between the DC voltage and the energy-storage stepped voltage.As the difference decreased,the switching frequency reduced.The MSFT control strategy was designed by incorporating a fixed-step gradient-descent algorithm into the original DC voltage control strategy.This strategy searched for the DC operating point and minimized the switching frequency.Meanwhile,to address potential parameter inconsistencies among the sub-modules,an improved valve control strategy was designed.The sub-modules could take turns performing switching tasks,thereby balancing the state of charge(SOC)of the sub-module batteries and eliminating the impact of sub-module placement on the output voltage of HVDC-DCES.Finally,an optimization design method for several main circuit and control parameters of HVDC-DCES was proposed. Simulation results for the flexible DC transmission system with HVDC-DCES showed that replacing the rounding control with hysteresis control reduced the HVDC-DCES switching frequency from 20 kHz to 12.5 kHz.When the ratio of the hysteresis loop width b to the current loop proportional control coefficient kp is 0.02,the output current ripple amplitude was limited to 0.01 in per unit,which was consistent with the calculation formula.At the same time,as the DC voltage gradually increased,the relationship between the switching frequency and the voltage difference conformed to the derived formula.After adopting MSFT control,the switching frequency was reduced from 12.5 kHz to about 500 Hz,the switching power loss of the IGBT devices was reduced by about 96%,and the DC voltage was reduced by only 0.65%.When a DC power disturbance was applied,or the sub-module battery capacity was reduced,MSFT control could still effectively reduce the switching frequency.Finally,the hardware-in-the-loop(HIL)test results were consistent with the simulation results. The following conclusions can be drawn.(1)After replacing the rounding control with hysteresis control,the switching frequency of HVDC-DCES is reduced,and the ripple amplitude of the output current and the switching frequency are consistent with the proposed calculation formulas.(2)MSFT control can significantly reduce the switching frequency of the HVDC-DCES by adjusting the DC voltage.It has anti-interference capability that prioritizes maintaining DC voltage stability when disturbances occur in the DC system.(3)When the terminal voltage of the sub-modules of HVDC-DCES changes,MSFT control can quickly track the voltage change and effectively reduce the switching frequency.
芦文泽;季柯;韩民晓;熊凌飞;陈思齐
华北电力大学电气与电子工程学院 北京 102206华北电力大学电气与电子工程学院 北京 102206华北电力大学电气与电子工程学院 北京 102206国网经济技术研究院有限公司 北京 102209国网经济技术研究院有限公司 北京 102209
信息技术与安全科学
高压直流直挂储能柔性直流系统开关频率最低开关频率追踪
High-voltage DC direct-connected energy storageflexible high-voltage DC transmission systemswitching frequencyminimum switching frequency tracking
《电工技术学报》 2026 (16)
5622-5638,17
智能电网国家科技重大专项资助项目(2024ZD0800200).