不对称故障下基于模型预测控制和谐振控制器的构网型变流器故障穿越方法OA
Fault Ride-Through Method for Grid-Forming Converters Based on Model Predictive Control and Resonant Control Under Asymmetrical Fault
构网型(GFM)变流器在不对称故障下会产生较大的故障电流,并且电网故障引入的负序分量会严重限制系统的控制性能.传统基于虚拟阻抗的电流抑制策略不仅会改变系统全频率段的等效阻抗,还会对稳态电流产生影响,进而降低故障穿越(FRT)期间无功功率支撑的动态响应速度.此外,在稳态时,传统方法需要依靠额外的负序电流提取来处理系统中的负序分量,这增加了系统的复杂度.该文提出一种基于模型预测控制(MPC)和谐振控制器的构网型变流器故障穿越方法.该方法通过谐振控制器与 MPC 的协同控制,能够精确抑制对称和不对称故障引发的暂态电流,同时不会对稳态电流造成影响,具备更快的无功功率响应速度.在稳态时,通过包含电压与电流控制的多变量代价函数,所提方法仅需调整负序端电压的参考值即可实现不同的控制目标,无需对反馈的电压和电流进行额外的正负序提取.所提方法的有效性在 3.5 kW 并网发电实验平台上得到了验证.
Grid-forming(GFM)converters under asymmetric faults generate significant fault currents,where negative-sequence components impair system control.Traditional virtual-impedance-based current suppression alters system-wide equivalent impedance and affects steady-state current,thereby limiting dynamic reactive power support during fault ride-through(FRT).Moreover,conventional methods require additional negative-sequence extraction,increasing complexity.This paper proposes an FRT strategy combining model predictive control(MPC)with a resonant controller.The method suppresses transient currents under both symmetrical and asymmetrical faults through coordinated control,without affecting steady-state performance,enabling faster reactive power response.Under steady state,it achieves flexible control objectives by adjusting negative-sequence voltage references via a multivariable cost function without explicit sequence extraction.Validation on a 3.5 kW grid-connected experimental platform confirms its effectiveness. The system behavior under asymmetrical faults is first analyzed.At the instant of fault occurrence,the voltage difference between the terminal voltage and the grid voltage induces a large fault current,which consists of a decaying DC offset and a steady-state AC component,as derived from a first-order differential equation.Under steady-state fault conditions,positive-and negative-sequence grid voltage components generate negative-sequence current,and their interaction introduces double-frequency oscillations in the output power. To ensure that the voltage reference output by the VSG does not contain negative-sequence components,a notch filter is applied to the feedback power.Based on the DC characteristic of the transient current,a high-pass filter in the synchronous reference frame extracts the transient component,which is then fed back to the positive-sequence capacitor voltage reference through a resonant controller.This transient suppression strategy is effective under both symmetrical and asymmetrical faults.In steady-state operation,this paper sets four control objectives under asymmetric fault conditions:no negative-sequence current;absorb negative-sequence reactive current;constant reactive power;and constant active power.The relationship between the output negative-sequence terminal voltage and the grid voltage is derived.Using the extracted positive-and negative-sequence components of the grid voltage,the corresponding negative-sequence voltage references are computed and then converted into current references.All voltage and current references are incorporated into a unified multivariable cost function in the stationary frame,where the optimal voltage vector is selected to drive the inverter.The proposed method only needs to modify the reference value of the negative-sequence component.It does not need to extract the positive-and negative-sequence components of the feedback signal,thereby simplifying the control structure. Experimental comparisons with a virtual-resistance-based FRT method show that,under an 80%single-phase voltage dip,the proposed strategy achieves a reactive power response time of 40 ms,compared to 70 ms with the virtual-resistance method.During grid restoration,the active power response time is 50 ms,significantly shorter than the 150 ms of the conventional method.Under steady-state testing,the proposed strategy fulfills the four control objectives,as evidenced by improvements in grid current unbalance,negative-sequence reactive current,and deviations in active and reactive power.
蒋涛;张永昌
华北电力大学电气与电子工程学院 北京 102206华北电力大学电气与电子工程学院 北京 102206
信息技术与安全科学
模型预测控制构网型变流器虚拟同步机故障穿越不对称故障
Model predictive control(MPC)grid-forming(FGM)convertervirtual synchronous generator(VSG)fault ride-through(FRT)asymmetrical fault
《电工技术学报》 2026 (16)
5609-5621,13