首页|期刊导航|电工技术学报|弱电网下采用对称锁相环的并网逆变器稳定性分析与改进控制策略

弱电网下采用对称锁相环的并网逆变器稳定性分析与改进控制策略OA

Stability Analysis and Improved Control Strategy of Grid-Connected Inverters Using Symmetric Phase-Locked Loop under Weak Grid

中文摘要英文摘要

相比传统同步参考坐标系锁相环(SRF-PLL),对称锁相环(SPLL)因其控制结构对称,具有消除频率耦合的优势,但这种对称结构对弱电网下逆变器并网系统的稳定性影响有待研究.为此,该文首先基于并网系统小信号模型中存在的"SPLL—电流环—电网阻抗—并网点电压—SPLL"闭环耦合关系,从 SPLL 动态特性角度建立并网系统的等效复转矩模型.其次,基于表征SPLL 动态特征方程,推导出主导振荡模式阻尼的解析表达式,并将其分解为采用 SRF-PLL 的并网系统固有阻尼和 dq 轴控制耦合引入的附加阻尼两部分,理论分析表明,弱电网下该附加阻尼呈现负阻尼特性,且随着电网强度减弱而加剧,恶化了系统的稳定性.进一步地,提出一种具有对称结构的改进电流环控制策略,并设计相应的补偿控制器,该策略在维持控制结构对称性的同时,能够有效补偿由 dq 轴控制耦合引入的负阻尼,从而增强弱电网下系统的稳定性.最后,搭建基于RT-Lab的硬件在环实验平台并进行实验,实验结果验证了理论分析的正确性及所提控制策略的有效性.

The growing integration of renewable energy sources has spurred widespread adoption of grid-connected inverters.However,the dynamic interaction between these inverters and weak grids introduces new stability challenges.The symmetrical phase-locked loop(SPLL)incorporates an additional d-axis control loop,achieving a symmetrical control structure that effectively eliminates the frequency coupling inherent in the traditional synchronous reference frame phase-locked loop(SRF-PLL).Although the symmetrical structure of the SPLL provides significant benefits,its impact on the stability of three-phase grid-connected systems under weak-grid conditions remains to be explored.The complex vector impedance model is commonly employed to evaluate the effect of the SPLL structure on the stability of grid-connected systems.However,this modelling method obscures the internal dq-axis dynamic coupling within the SPLL.In particular,the effect of the additional d-axis control remains unclear.Therefore,a new modeling method and analytical framework are required to elucidate the causes of instability and develop corresponding stabilization strategies. To begin with,the closed-loop coupling relationship among the"SPLL-current loop-grid impedance-PCC voltage-SPLL"is investigated.From the perspective of SPLL dynamics,the SPLL-based system can be equivalently represented by a dq-axis-coupled double-complex torque model.This model reveals that the d-axis control of the SPLL introduces a critical closed-loop dynamic coupling path of"q-axis→d-axi→q-axis".Compared with the complex torque model,the additional damping introduced by this path is identified as the key factor driving the differing impacts of the two PLLs on grid-connected system stability under weak grid conditions.Furthermore,from a quantitative perspective,the damping of the dominant oscillation mode in the SPLL-based system is decomposed into two components:the inherent damping of an SRF-PLL-based system and the additional damping introduced by the dq-axis control coupling.Under weak-grid conditions,this additional damping component introduces negative damping,and its magnitude increases with rising grid impedance.Therefore,this negative damping constitutes the root cause of oscillatory instability in the SPLL-based system. This paper proposes an improved current-loop control strategy with a symmetrical structure to enhance system stability.In this strategy,the phase perturbation from the SPLL is utilized as a feedforward input for a dedicated compensation controller,which injects corrective terms into both the d-axis and q-axis current loops.These terms are designed to cancel the component of output current disturbance that is directly induced by the SPLL phase perturbation,thereby weakening the critical"PLL-current loop"coupling path.Consequently,the negative damping component introduced by the dq-axis coupling in the equivalent complex torque is significantly attenuated.Furthermore,by appropriately tuning the compensation controller parameters,the improved grid-connected system exhibits enhanced robustness against grid impedance variations while maintaining excellent dynamic and transient performance. Finally,a hardware-in-the-loop experimental platform is constructed based on RT-Lab.The experimental results demonstrate that the proposed improved current-loop control strategy ensures system stability under weak-grid conditions by effectively suppressing oscillations.Meanwhile,in dynamic scenarios involving sudden grid voltage sags and grid frequency fluctuations,the system with the proposed control strategy maintains excellent robustness and dynamic performance,confirming its effectiveness across different operating conditions.

解润生;解宝;张国荣;杜燕

合肥工业大学电气与自动化工程学院 合肥 230009合肥工业大学电气与自动化工程学院 合肥 230009合肥工业大学电气与自动化工程学院 合肥 230009合肥工业大学电气与自动化工程学院 合肥 230009

信息技术与安全科学

对称锁相环并网逆变器复转矩模型阻尼特性补偿控制器

Symmetric phase-locked loopgrid-connected invertercomplex torque modeldamping chara-cteristicscompensation controller

《电工技术学报》 2026 (16)

5593-5608,16

国家重点研发计划(2021YFB2601403)和安徽省自然科学基金(2208085QE165)资助项目.

10.19595/j.cnki.1000-6753.tces.251573

评论