首页|期刊导航|高电压技术|考虑极性效应及电弧多次重燃的残余电压特性对VFTO的影响

考虑极性效应及电弧多次重燃的残余电压特性对VFTO的影响OA

Influence of Trapped Charge Voltage Characteristics on VFTO Considering Polarity Effect and Multiple Arc Reignitions

中文摘要英文摘要

气体绝缘开关设备(gas insulated switchgear,GIS)隔离开关操作过程中负载侧的残余电压显著影响特快速暂态过电压(very fast transient overvoltage,VFTO)的幅值、波形等特征,深入研究其变化规律有助于更准确地掌握VFTO的特性.该文以某特高压GIS为原型,通过对重复击穿过程进行数学描述,获得了残余电压与隔离开关速度及击穿电压极性之间的关系.建立了考虑间隙击穿电压极性效应的隔离开关多次重燃的电弧模型,通过与IEC典型试验回路的实测波形对比,验证了模型的准确性.基于上述模型,仿真研究了开关速度和极性特性对残余电压变化规律的影响,并进一步分析了残余电压对重复击穿过程中VFTO波形及幅值的影响.研究结果表明:操作速度较快时,残余电压水平较高,进而使得VFTO的幅值较大;残余电压受正、负极性击穿电压比值的影响呈现出不同的变化规律,导致操作过程中的VFTO最大值未必总是在分闸末次或合闸首次击穿时出现.正、负极性击穿电压比值较大时,产生的残余电压幅值较小.当比值趋近于1时,分合闸过程中可能会发生最严重的击穿工况.因此通过增大击穿电压比值可降低残余电压的幅值,从而降低VFTO水平.

The trapped charge voltage during a gas insulated switchgear(GIS)disconnector operation significantly in-fluences the characteristics of the very fast transient overvoltage(VFTO),such as its amplitude and waveform,and in-depth study of its variation law is essential for accurately characterizing VFTO.Consequently,using an ultra-high voltage GIS as a prototype,we derived the relationship between trapped charge voltage,disconnector speed,and break-down voltage polarity via mathematical description of repeated breakdown processes.An arc model for disconnector multiple restrikes,considering the polarity effect of gap breakdown voltage,was established,and its accuracy was verified by comparison with measured waveforms of the IEC typical test circuit.Based on this model,the influences of switch speed and polarity characteristics on trapped charge voltage variation laws were studied by simulation,and the impact of trapped charge voltage on VFTO waveform and amplitude during repeated breakdown was further analyzed.The results indicate that a higher operating speed leads to an elevated trapped charge voltage level,consequently resulting in an in-creased VFTO magnitude;trapped charge voltage exhibits different variation laws with the positive-to-negative breakdown voltage ratio,so the maximum VFTO during operation does not necessarily occur in the last opening or first closing breakdown.When the ratio is large,trapped charge voltage amplitude is small;when approaching 1,the most se-vere breakdown conditions may occur during both opening and closing operations.Thus,increasing the ratio can reduce the trapped charge voltage amplitude,and lower the VFTO level.

刘青;罗浩;李奥龙;李志杰;仇志伟

西安科技大学电气与控制工程学院,西安 710054西安科技大学电气与控制工程学院,西安 710054西安科技大学电气与控制工程学院,西安 710054西安科技大学电气与控制工程学院,西安 710054西安科技大学电气与控制工程学院,西安 710054

特快速暂态过电压分段电弧模型残余电压击穿电压极性效应

very fast transient overvoltagesegmented arc modeltrapped charge voltagebreakdown voltagepolarity effect

《高电压技术》 2026 (7)

3384-3394,11

国家重点研发计划(2023YFC3009802).Project supported by National Key R&D Program of China(2023YFC3009802).

10.13336/j.1003-6520.hve.20251239

评论