首页|期刊导航|高电压技术|弱电网下多功能并网逆变器的加权谐振容压前馈控制策略

弱电网下多功能并网逆变器的加权谐振容压前馈控制策略OA

Weighted Resonant Capacitive Voltage Feedforward Control Strategy for Multifunctional Grid-connected Inverters Under Weak Grid

中文摘要英文摘要

多功能并网逆变器具有基于谐波检测的输出电流调制的功能,常用于改善强电网的电能质量.然而,在弱电网条件下,随着电网阻抗波动,电网电压会产生显著的背景谐波,进而造成逆变器并网电流畸变.传统采用电容电压前馈控制策略的方法可有效抑制弱电网下的背景谐波,但会引入前馈通路,进而降低系统的稳定性.针对上述问题,提出了一种加权谐振容压前馈控制策略,可有效抑制背景谐波并提高系统稳定性.首先,对基于传统电容电压前馈控制策略的多功能并网逆变器控制系统进行数学建模,并通过幅相频率特性曲线分析系统稳定性;其次,通过2阶前馈通路串联PR控制器以重塑系统幅相频率特性曲线,从而改善电能质量,抑制谐波并提高系统稳定性.同时,考虑系统输出阻抗与电网阻抗的耦合效应,使用阻抗分析法进行系统阻抗建模,分析弱电网下改进控制策略多功能并网逆变器系统的失稳原因,并基于此提出一种加权谐振容压前馈控制策略.然后,使用模拟退火算法计算加权因子,并引入比例前馈及2阶前馈通路,进一步提升系统在阻抗波动下的鲁棒性.最后,通过仿真验证阻抗波动下所提出控制策略的有效性.

Multifunctional grid-connected inverters are able to modulate their output current by utilizing the harmonic detection,therefore are commonly used to improve the power quality in strong grids.However,under weak grid condi-tions and grid impedance fluctuations,significant background harmonics of grid voltage will be generated,distorting the output current of these inverters.The background harmonic problem under weak grid can be effectively suppressed by using existing capacitor voltage feed-forward control strategy,but the existence of feedforward path will worsen the sys-tem stability.To address these issues,this paper proposes a weighted resonant capacitive voltage feedforward control strategy,which can effectively suppress the background harmonics and improve the system stability.Firstly,a multifunc-tional grid-connected inverter control system based on the existing capacitive voltage feedforward control strategy is mathematically modeled,and the system stability is analyzed by using the magnitude/phase-frequency characteristic curve.Secondly,a PR controller is connected in series in the second-order feedforward path to reshape the magni-tude/phase-frequency characteristic curve of the system,so as to improve the power quality,suppress the harmonics and improve the system stability.At the same time,the coupling effect between the system output impedance and the grid im-pedance is taken into consideration,and the impedance analysis method is used for system impedance modelling to analyze the causes of instability of the multifunctional grid-connected inverter system with improved control strategy un-der a weak grid.On this basis,a weighted resonant capacitive-voltage feedforward control strategy is proposed.A simulated annealing algorithm is used to calculate the weighting factor and the proportional feedforward and second-order feedforward paths are introduced to further improve the robustness of the system under impedance fluctuations.Finally,the effectiveness of the proposed control strategy under impedance fluctuation is verified by simulations.

张宇坤;白雅楠;冯博文;黄越辉;杨景熙;李守翔

北京理工大学自动化学院,北京 100081北京理工大学自动化学院,北京 100081北京理工大学自动化学院,北京 100081中国电力科学研究院有限公司,北京 100192香港城市大学,香港 999077北京理工大学自动化学院,北京 100081

阻抗波动背景谐波多功能跟网逆变器电压前馈加权谐振容压前馈控制模拟退火算法

impedance fluctuationbackground harmonicsmultifunctional grid-connected invertervoltage feedforwardweighted resonant capacitance pressure feedforward controlsimulated annealing algorithm

《高电压技术》 2026 (7)

3267-3276,中插19,11

国家自然科学基金(62473045).Project supported by National Natural Science Foundation of China(62473045).

10.13336/j.1003-6520.hve.20242039

评论