换热面积对高温热泵性能影响的模拟研究OA

Simulation Study on Influence of Heat Exchange Area on Performance of High-Temperature Heat Pumps

中文摘要英文摘要

采用白箱模型与黑箱模型耦合的混合建模方式,建立高温热泵混合模型.结合算例,对蒸发器面积、冷凝器面积对热泵运行性能的影响进行分析,选取兼顾热泵性能与经济性的临界蒸发器面积与临界冷凝器面积.冷凝器面积一定时,蒸发温度随蒸发器面积增大先快速增大然后趋于平缓.蒸发器面积一定时,冷凝器面积对蒸发温度的影响很小.蒸发器面积一定时,冷凝温度随冷凝器面积增大先快速下降然后趋于平稳.冷凝器面积一定时,蒸发器面积对冷凝温度的影响很小.冷凝器面积一定时,热泵制热量随蒸发器面积增大先快速增大然后趋于平缓.蒸发器面积一定时,冷凝器面积对热泵制热量的影响很小.冷凝器面积一定时,热泵制热性能系数随蒸发器面积增大先快速增大然后趋于平缓.蒸发器面积一定时,热泵制热性能系数随冷凝器面积增大而增大,但增长速率呈放缓趋势.增大蒸发器面积可提高蒸发温度,增大冷凝器面积可降低冷凝温度,从而提升热泵性能,但存在临界值,超过临界值后继续增大蒸发器面积、冷凝器面积不但导致投资增加,而且无法进一步有效提高蒸发温度、降低冷凝温度.

A hybrid modeling approach coupling white-box models and black-box models is adopted to establish a hybrid model of the high-temperature heat pump.Combined with calculation examples,the influ-ences of evaporator area and condenser area on the operating performance of the heat pump are analyzed,and the critical evaporator area and critical condenser area that balance heat pump performance and eco-nomic efficiency are selected.When the condenser area is fixed,the evaporation temperature increases rapidly at first and then levels off with the increase of evaporator area.When the evaporator area is fixed,the condenser area exerts little influence on the evapora-tion temperature.When the condenser area is fixed,the heating capacity of the heat pump increases rapidly at first and then levels off with the increase of evapora-tor area.When the evaporator area is fixed,the con-denser area imposes little effect on the heating capac-ity.When the condenser area is fixed,the heating coef-ficient of performance(COP)of the heat pump increases rapidly at first and then levels off with the increase of evaporator area.When the evaporator area is fixed,the heating COP of the heat pump increases with the increase in condenser area,but the growth rate slows down gradually.Increasing the evaporator area can raise the evaporation temperature,and increasing the condenser area can reduce the condensation tem-perature,thereby improving heat pump performance.However,there exists a critical value.Beyond this criti-cal value,further increasing the evaporator or con-denser areas will not only lead to higher investment but also fail to effectively further raise the evaporation tem-perature or lower the condensation temperature.

靳茗森;胡晓微;董胜明;胡朋丽;宋美洁

天津商业大学机械工程学院,天津 300134天津商业大学机械工程学院,天津 300134||天津市制冷技术重点实验室,天津 300134天津商业大学机械工程学院,天津 300134||天津市制冷技术重点实验室,天津 300134天津商业大学机械工程学院,天津 300134天津商业大学机械工程学院,天津 300134

建筑与水利

高温热泵蒸发器面积冷凝器面积

high-temperature heat pumpevaporator areacondenser area

《煤气与热力》 2026 (6)

7-12,6

承德市重大科技成果转化专项资助项目(202306B002)

评论