首页|期刊导航|电工技术学报|特高压快速断路器凸起型陷阱与阶梯加压老炼程序协同优化设计

特高压快速断路器凸起型陷阱与阶梯加压老炼程序协同优化设计OA

The Coordinated Optimization Design of Raised-Type Particle Trap and Stepwise Voltage Conditioning Method for UHV Fast-Acting Circuit Breaker

中文摘要英文摘要

快速断路器作为新一代气体绝缘开关设备(GIS),其小型化结构虽提升了开断性能,但也使其内部金属微粒在高电场下更易起举并加速运动,在入陷前诱发放电.因此,该文首先提出一种适用于 800 kV 快速断路器的曲面结构凸起型微粒陷阱设计方案,综合考虑绝缘裕度、微粒捕获与机械应力等因素,将结构参数优化为:厚度 3 mm、圆周角 40°、提上高度 5 mm、槽孔尺寸 30 mm×5 mm,并布设于断口下方与气室端部等关键绝缘区域.仿真结果表明,该陷阱结构在满足典型微粒尺寸捕获需求的同时,也不影响设备原本的绝缘裕度.同时,基于设备的内部电场分布情况,提出微粒安全运动高度阈值为 10 cm,并基于微粒入陷仿真构建阶梯加压老炼程序,该程序涵盖 6 个电压阶梯(280~700 kV),耐压时间 1~5 min,升压速率 10 kV/s.然后,搭建800 kV 快速断路器真型试验平台,结合高速摄像与超声检测技术开展验证试验,结果表明微粒可稳定入陷,整个耐压过程中未发生放电事件.与直接升压方式相比,微粒运动信号强度降低 38%.该研究成果可为快速断路器绝缘设计及 GIS 微粒抑制提供理论与工程支持.

The fast-acting circuit breaker(FACB),as a new generation high-voltage switching device in gas-insulated switchgear(GIS),is widely deployed in ultra-high-voltage DC transmission systems.Its increasingly compact structure significantly reduces internal insulation gaps,posing critical challenges to insulation reliability.During operation and testing,residual or generated metallic particles can easily lift and accelerate under high electric fields,becoming a major source of partial discharges or dielectric breakdown.Engineering experience indicates that,during power frequency withstand tests,if particles are not securely trapped in advance,direct voltage application may induce discharge and obscure latent defects.Therefore,it is crucial to develop a coordinated strategy integrating particle traps with voltage conditioning procedures to ensure particle suppression prior to high-voltage application. To address this,a curved-structure protruded particle trap specifically designed for 800 kV FACB is proposed.Simulation of local electric fields and particle trajectories reveals a dual trapping mechanism combining low-field zones and physical obstructions.Without compromising insulation margins,key structural parameters were optimized—trap thickness of 3 mm,circumferential angle of 40°,height of 5 mm,and slot dimensions of 30 mm × 5 mm—with the trap installed near the interrupter gap and enclosure ends.Simulation results confirm this design balances trapping efficiency and structural reliability,making it well-suited for engineering application. Further field analysis revealed a low-gradient zone approximately 10 cm above the ground electrode,serving as a safe particle movement region.Based on this,the particle safety height was defined.Trajectory simulations were then conducted for representative particle types(spherical:0.5~1 mm;linear:0.1~1 mm;flake:0.15~0.3 mm thick),and their corresponding safe trapping voltages were determined.A stepwise voltage conditioning program was proposed and refined into six voltage steps—280 kV,350 kV,420 kV,500 kV,630 kV,and 700 kV—with durations of 1~5 min and a ramp rate of 10 kV/s. Validation experiments were conducted on a full-scale 800 kV FACB platform.High-speed imaging and ultrasonic sensing confirmed that all particles were stably captured within their respective voltage stages,with no re-lifting or discharge events observed.Compared to direct voltage application,the proposed method reduced particle motion signal intensity by up to 38%.These results verify the practical effectiveness and engineering value of the proposed trap structure and stepwise conditioning program,offering theoretical and technical guidance for insulation reliability improvement in FACB and GIS applications.

耿秋钰;王健;李庆民;边亚琳;傅中

新能源电力系统全国重点实验室(华北电力大学) 北京 102206新能源电力系统全国重点实验室(华北电力大学) 北京 102206新能源电力系统全国重点实验室(华北电力大学) 北京 102206中国电力科学研究院有限公司 北京 100192国网安徽省电力有限公司电力科学研究院 合肥 230600

信息技术与安全科学

特高压快速断路器凸起型陷阱阶梯加压老炼程序真型试验

UHVfast-acting circuit breakerraised-type trapstepwise voltage rampingconditioning methodfull-scale experiment

《电工技术学报》 2026 (9)

3170-3182,13

国家电网有限公司科技项目资助(5500-202355794A-3-8-KJ).

10.19595/j.cnki.1000-6753.tces.250654

评论