高土壤电阻率山区输电管廊接地特性研究OA
Grounding Characteristics of Transmission Pipeline Corridors in High Soil Resistivity Terrain
管廊输电在解决新能源外送难题中具有重要意义,其接地系统关系到设备安全运行.本研究使用CDEGS建模,系统分析了土壤电阻率、管廊长度及贯通地线与主结构钢筋的跨接距离对接地系统电气特性的影响.结果表明,土壤电阻率升高导致接地阻抗线性增加,在短管廊中增速更快;管廊长度增加可逐渐降低接地阻抗,但当管廊长度超过4 km后,降阻效果不再明显;缩短贯通地线与主结构钢筋的跨接距离能有效降低接地阻抗,其中100~125 m的跨接距离较适宜.综合对比管廊人工与盾构接地系统的电气特性,发现在高土壤电阻率长距离输电环境下,盾构接地系统更有效控制管廊内电压分布.本研究为高电阻地区输电管廊的接地方案优化提供了理论支持,有助于输电管廊的安全稳定运行.
Power transmission in pipeline corridors is of great significance in solving the problem of new energy transmission,and its grounding system is related to the safe operation of the equipment.The au-thor uses CDEGS modeling to systematically analyze the effects of soil resistivity,length of the pipeline corridor,and spanning distance between the through ground and the main structural reinforcement on the electrical characteristics of the grounding system.The results show that the increase of soil resistivity leads to the linear increase of grounding impedance,and the growth rate is faster in short corridors;the increase of corridor length can gradually reduce the grounding impedance,but when the length of the hall is more than 4 km,the effect of resistance reduction is no longer apparent;the shortening of the spanning distance between the ground penetration line and the reinforcement bars of the main structure can effec-tively reduce the grounding impedance,in which the spanning distance of 100~125 m is more suitable.A comprehensive comparison of the electrical characteristics of the artificial and shield grounding systems in the pipeline corridor found that the shield grounding system is more effective in controlling the voltage distribution in the pipeline corridor in a high-resistance long-distance power transmission environment.The research provides theoretical support for optimizing the grounding scheme for transmission corridors in high-resistance areas,which contributes to the safe and stable operation of transmission corridors.
范荣全;曾文慧;邹斌;李果;许文杰;黄珂琦
国网四川省电力公司经济技术研究院,成都 610041||国网四川省电力公司,成都 610041国网四川省电力公司经济技术研究院,成都 610041||国网四川省电力公司,成都 610041国网四川省电力公司经济技术研究院,成都 610041||国网四川省电力公司,成都 610041国网四川省电力公司经济技术研究院,成都 610041||国网四川省电力公司,成都 610041国网四川省电力公司经济技术研究院,成都 610041||国网四川省电力公司,成都 610041西南交通大学电气工程学院,成都 610031
输电管廊高土壤电阻率盾构接地系统人工接地系统接地阻抗电压分布
transmission pipeline corridorhigh soil resistivityshield grounding systemartificial grounding systemgrounding impedancevoltage distribution
《电瓷避雷器》 2026 (2)
56-66,11
国网四川省电力公司科技项目(编号:521996220002).Project supported by Science and Technology Project of State Grid Sichuan Electric Power Company(No.521996220002).
评论