首页|期刊导航|电瓷避雷器|基于输电线路布局优化的管道过电压防护

基于输电线路布局优化的管道过电压防护OA

Pipeline Overvoltage Protection Based on Optimization of Transmission Line Layout

中文摘要英文摘要

输电线路发生单相接地故障时,平行埋地油气管道存在明显的电磁感应电压.针对上述问题,文中研究了输电线路参数对埋地管道电磁干扰的影响规律.采用CDEGS仿真软件搭建了输电线路与埋地管道模型,分析了杆塔接地网模型、相线及地线对地高度、故障电流、故障位置、输电线路与埋地管道平行间距、架空地线接地方式等因素对管道涂层感应电压的影响.仿真结果表明,增大平行间距以及架空地线采用逐塔接地方式能够有效降低管道涂层感应电压,该结论可为输电线路的设计以及埋地管道的安全防护提供参考.

After a single phase-to-ground fault occurs on a transmission line,the adjacent buried oil and gas pipelines suffer a significant electromagnetic induced voltage.Aiming at the above problems,the influence of transmission line parameters on electromagnetic interference of buried pipelines is studied.The simulation models of transmission line and buried pipeline are established in CDEGS simulation soft-ware.The influence of factors such as tower grounding model,height of phase and ground lines,fault current,fault location,parallel distance between transmission line and buried pipeline,and grounding mode of overhead ground wire on pipeline coating induced voltage is studied in detail.According to a large number of simulations,the following characteristics are summarized.The induced voltage of pipe-line coating effectively decreases with the increase of parallel distance between transmission lines and bur-ied pipelines.The conclusions are useful for the design of transmission lines and the safety protection of buried pipelines.

胡鑫;王英杰;席小娟;郭彦勋

国网河南省电力公司经济技术研究院,郑州 450052郑州大学电气与信息工程学院,郑州 450001国网河南省电力公司经济技术研究院,郑州 450052郑州大学电气与信息工程学院,郑州 450001

埋地管道输电线路单相接地故障涂层感应电压故障电流平行间距架空地线安全防护

buried pipelinetransmission linesingle-phase grounding faultcoating induced voltagefault currentparallel spacingoverhead ground wiresafety protection

《电瓷避雷器》 2026 (2)

1-7,7

国家自然科学基金资助项目(编号:52107130).Project supported by National Natural Science Foundation of China(No.52107130).

10.16188/j.isa.1003-8337.2026.02.001