微粒缺陷引发220 kV GIS绝缘击穿的事故分析及预防措施OA

Analysis and Preventive Measures of Insulation Breakdown Accident Caused by Particle Defects in 220 kV GIS

中文摘要英文摘要

GIS作为电力系统的关键设备之一,其运行的安全可靠至关重要.对某电厂一起220 kV GIS电缆仓内绝缘击穿事故进行分析,根据故障录波图判断,该事故为先发生了单相接地短路,而后发展为三相短路故障.综合解体和检测情况,复原事故过程为:运行过程中,气室内有异物掉落,进入电缆仓内强电场区域,使电场分布畸变,进而引发单相击穿;由于电缆仓和接地开关气室之间未设置气隔盆子,导致单相击穿后的金属融化液飞溅至接地开关支撑盆子上,引发事故扩大,发生三相短路.吸取该事故教训,提出选用不锈钢吸附剂盒、合理预留GIS内部非标部件绝缘裕度、加强设备状态巡检和评估等预防措施,为后续GIS的安全运行和设计优化提供实践依据.

GIS is one of critical equipment of power system and its safe and reliable operation is very important.The insulation breakdown in cable compartment of 220 kV GIS in a power plant is analyzed.It is concluded by the judgement of the fault recording diagram that single⁃phase grounding short circuit occurs firstly,followed by the three⁃phase short circuit.Based on the disintegration and detection,the accident process is analyzed as follows:dur⁃ing operation,foreign particle drops in the gas compartment and enters into the strong electric field area of the cable compartment,leading to electric field distribution and single⁃phase breakdown.Since no insulating barrier is set be⁃tween the cable compartment and the gas compartment of disconnector,the molten metal splashes onto the support spacer of the earthing switch after a single⁃phase breakdown,leading to the escalation of the accident and resulting in a three⁃phase short circuit.Drawing lessons from the accident,such preventive measures as selecting stainless steel adsorbent box,reasonably reserving insulation margin of non⁃standard parts in GIS,strengthening patrolinspec⁃tion and assessment of equipment status are proposed so to provide practical basis for safe operation and design opti⁃mization of GIS in the future.

雷志城;黄烜城;黄涛;陈敏哲;刘雨;石仁强

江苏方天电力技术有限公司,南京 211102江苏方天电力技术有限公司,南京 211102江苏方天电力技术有限公司,南京 211102江苏方天电力技术有限公司,南京 211102江苏方天电力技术有限公司,南京 211102江苏方天电力技术有限公司,南京 211102

GIS绝缘击穿解体分析异物掉落电场畸变预防措施

insulation breakdown in GISdisintegration analysisdropped particleelectric field distortionpreventive measures

《高压电器》 2026 (4)

229-236,8

10.13296/j.1001⁃1609.hva.2026.04.027

评论