洁净手术室空调系统温湿度独立控制方案探讨OA
Discussion on the independent temperature and humidity control scheme for clean operating room air conditioning system
传统洁净手术室空调系统存在温湿度耦合控制、能耗偏高等问题,亟需探索高效节能的控制方案.构建温湿度独立控制(THIC)系统方案,通过新风承担湿负荷、循环机组干工况运行,实现温湿度分离控制,并建立系统配置与空气处理工艺流程,以江西鹰潭某医院为研究对象进行节能分析.结果表明,THIC系统相比传统方案总冷量降低46.2%,循环再热量减少88.7%,其中Ⅰ级手术室年电耗降低52.3%,年减碳量达3.2 tCO2.温湿度独立控制系统有效避免冷热抵消现象,明显提升空气质量与节能效果,为医疗建筑绿色发展提供了技术途径.
The traditional air conditioning system for clean operating rooms has problems such as coupled temperature and humidity control and excessive energy consumption.It is urgent to explore efficient and energy-saving control schemes.A temperature and humidity independent control(THIC)system scheme is constructed,where fresh air takes on the moisture load and the circulating unit operates in dry conditions to achieve separate control of temperature and humidity.The system configuration and air treatment process are established,and an energy-saving analysis is conducted using a hospital in Yingtan,Jiangxi Province as the research object.The results show that compared with the traditional scheme,the total cooling capacity of the THIC system is reduced by 46.2%,the reheat capacity of the circulation unit is reduced by 88.7%,and the annual electricity consumption of the first-level operating room is reduced by 52.3%,with a carbon dioxide reduction of 3.2 tCO2 per year.The temperature and humidity independent control system effectively avoids the phenomenon of cold and hot counteraction,significantly improving air quality and energy-saving effect,providing a technical approach for the green development of medical buildings.
刘拴强
格瑞海思人居环境科技(江苏)有限公司,江苏 常州 213012
建筑与水利
温湿度独立控制洁净手术室节能分析空气质量
temperature and humidity independent controlclean operating roomenergy-saving analysisair quality
《节能》 2026 (1)
15-18,4
评论