特高压直流输电系统双极线路故障再启动逻辑优化与应用OA
Optimization and application of bipolar line fault restart logic for ultra high voltage direct current transmission systems
为防止特高压直流线路故障再启动导致交流电网产生稳定性风险,一极线路再启动时需要闭锁另一极线路的再启动逻辑,而两极直流控制系统互相传输闭锁命令时存在通信延时,当两极线路故障间隔时间小于极间通信延时时,将导致直流双极闭锁.因此,本文对线路故障再启动逻辑进行优化,引入最大极间通信延时参数,当实际极间通信延时小于最大极间通信延时时,直流控制系统可选择一极进行再启动.实时数字仿真试验和现场应用验证了优化逻辑的可行性,通过合理设置最大极间通信延时,可有效解决实际工程中双极线路短时相继故障导致双极闭锁的问题.
To prevent stability risks in the AC power grid caused by the fault restart of ultra high voltage direct current(UHVDC)lines,the restart of one pole needs to block the restart logic of the other pole.However,the transmission of blocking commands between the two DC control systems exsits communication delay.When the fault interval time between the two poles is less than the inter-pole communication delay,it will lead to the blocking of both poles.By optimizing the restart logic and introducing the maximum inter-pole communication delay parameter,the DC control systems can choose to restart one pole when the actual inter-pole communication delay is less than the maximum inter-pole communication delay.The real time digital simulation(RTDS)test and field application verify the feasibility of the optimized logic.By reasonably setting the maximum inter-pole communication delay,the problem of bipolar blocking caused by short-term successive faults in the two-pole lines in actual projects can be effectively solved.
LUO Jinhui;ZHANG Jing;FU Guangxu;PAN Weiming;WANG Yongping
NR Electric Co.,Ltd,Nanjing 211102NR Electric Co.,Ltd,Nanjing 211102NR Electric Co.,Ltd,Nanjing 211102NR Electric Co.,Ltd,Nanjing 211102NR Electric Co.,Ltd,Nanjing 211102
特高压直流(UHVDC)双极线路故障线路故障再启动直流控制系统直流可靠性
ultra high voltage direct current(UHVDC)bipolar line faultline fault restartDC control systemDC reliability
《电气技术》 2026 (1)